• India 3 Phase Error Electric Meter Testing Instruments for Site
  • India 3 Phase Error Electric Meter Testing Instruments for Site
  • India 3 Phase Error Electric Meter Testing Instruments for Site
  • India 3 Phase Error Electric Meter Testing Instruments for Site
  • India 3 Phase Error Electric Meter Testing Instruments for Site
  • India 3 Phase Error Electric Meter Testing Instruments for Site

India 3 Phase Error Electric Meter Testing Instruments for Site

Warranty: Three Years
Application: Thermal Power, Mechanical Instrument, Time Frequency Instrument, Electromagnetic Instrument
Power: Electricity
Certification: FDA, CE, IAF, CCC
Voltage Output: 500V
Current Output: 120A
Customization:
Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
GF302D
LCD Display
With LCD Display
Customized
Customized
Key Words
3 Phase Error Energy Instrument for Site
Key Word
Accuracy Test of Energy Meter
Model
Electric Meter Testing Instruments Manufacturers
Accuracy
0.05%, 0.1%
Measuring Accuracy
0.05%Rg
AC Current Output
200mA, 1A, 5A, 20A, 100A
Harmonic Number
2-51times
Active Power Pulse Output
5V, 10mA
Weight (Kg)
About 27
Transport Package
Standard Export Box
Specification
About 27 kg
Trademark
GFUVE
Origin
Beijing, China
Production Capacity
5000000pieces/Year

Product Description

Product description
India 3 Phase Error Electric Meter Testing Instruments for Site
India 3 Phase Error Electric Meter Testing Instruments for Site
India 3 Phase Error Electric Meter Testing Instruments for Site

The GF302D India manufacturers 3 phase error electric meter testing instruments for site is used for grid corporation of measurement and energy test center, management department of power supply bureau, national energy measurement of testing authorities, and also used to test each kind of single/three phase kWh meter of industries and mining enterprises as well as electric meter manufacturers. Meanwhile, the calibrator also can be used as one high precision standard power source.
Features
1. Able to test basic error, shunt running, start, standard error automatically and manually in single-step of single/three
phase, according to relative regulation of kWh meter.
2. Able to do change test caused by voltage influence, frequency influence and harmonic influence.
3. Output of power source is speedy and stable, AC maximum output of each phase can reach 120A in maximum.
4. Voltage, current and phase position of each phase can be adjusted in split-phase, improving the flexibility of
power source.
5. Frequency of each impulse input port can reach 40Hz.
6. 7-inch TFT color display touch screen, English menu, simple and convenient operation, commonly used functions
and current basic load point can be controlled in one button.
ti-7. Each meter position can provide one standard, dependent RS485 port, and able to do mul-function test such as communication test.
8. Impulse port of each meter position, external polarity can be set randomly, able to adapt kWh meter of impulse cascade and common-anode.
Parameters
Electrical parameters  
Accuracy 0.05%, 0.1%
Power Supply One Phase AC 180-265V, frequency 50/60Hz.
AC Voltage Output
Range(U1,U2,U3) 57.7V, 100V, 220V, 380V
or 69.3V, 120V, 240V, 480V( optional)
Adjustment range (0-120)%RG(1)
Adjustment fineness 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability 0.01%/120s
Distortion 0.3% (Non-capacitive load)
Output load each phase 25VA
Measuring accuracy 0.05%RG
AC Current Output
Range(I1,I2,I3) 200mA, 1A, 5A, 20A, 100A
Adjustment range (0-120)%RG
Adjustment fineness 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability <0.01%/120s
Distortion ≤0.3% (Non-capacitive load)
Output load 45VA
Accuracy 0.05%RG
Power Output 
Active power output stability <0.01%RG/120s
Reactive power output stability <0.02%RG/120s
Active power measuring accuracy  0.05%RG
Reactive power measuring accuracy 0.1%RG
Phase Output 
Output adjustment range 0°-359.999°
Output adjustment fineness 10, 1, 0.1, 0.01 as optional.
Resolution 0.01°
Accuracy 0.05°
Power Factor
Adjustment range -1 ~ 0 ~ 1
Resolution 0.0001
Measurement accuracy 0. 0005
Frequency Output 
Adjustment range 45Hz-65Hz
Output adjustment fineness 5Hz, 1Hz, 0.1Hz, 0.01Hz as optional.
Resolution 0.001Hz
Accuracy 0.005Hz
Voltage /Current/Harmonic Setting
Harmonic number 2-51times
Harmonic content 0-40%
Harmonic phase 0-359.99
Harmonic setting accuracy (10%±0.1%)RD(2)
Power Energy Measurement Error
Active power energy 0.05%RG
Reactive power energy 0.1%RG
Power Pulse Output 
Power pulse type active pulse, reactive pulse
Active power pulse output  5V,  10mA
Power Pulse Input
Energy pulse type support active and reactive pulse, the highest frequency power pulse input is 180K.
Mechanical parameters
Dimensions (W×D×H) (mm) 500x600x175
Weight (kg) About 27
(1) RG means range, the same as below;
(2) RD means the setted harmonic content, harmonic can be a single output, also multiple output.

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now