Gold Member Since 2013
Audited Supplier
Beijing GFUVE Electronics Co., Ltd.

Primary Current Injection Test Set, Large Current Injection Test Set, Current Injection Test Set manufacturer / supplier in China, offering High Current Primary Current Injection Test Set, 200A High Quality Compact Current Clamp Adapter, MID Vlotage Split Current Transformer and so on.

(/ )

Supplier Homepage Product Relay Test Set Others Relay Test Set High Current Primary Current Injection Test Set

High Current Primary Current Injection Test Set

FOB Price: Get Latest Price
Min. Order: 1 Piece
Production Capacity: 100sets/Month
Transport Package: Wooden Pallet
Payment Terms: L/C, T/T, D/P, Western Union, Paypal, Money Gram

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: TEST-901
  • Display: Digital
  • Power Supply: AC 220V±10%-25A
  • Current Output: AC 1000A-5V or 500A-10V
  • Waveform Distortion: <5%
  • Primary Current Range: 0-1100A
  • Secondary Current Range: 0-6A
  • Trademark: GFUVE
  • Origin: Beijing China
  • Accuracy Grade: 0.2%
  • Weight: 0-100Kg
  • Frenquency: 50Hz/60Hz
  • Capacity: 5kVA
  • Accuracy: 0.5%
  • Primary Current Resolution: 0.1A
  • Secondary Current Resolution: 0.001A
  • Specification: CE, ISO9001, IEC
Product Description
TEST-901 LARGE CURRENT 1000A PRIMARY CURRENT INJECTION TEST SET
High Current Primary Current Injection Test Set
High Current Primary Current Injection Test Set
High Current Primary Current Injection Test Set
Product description
TEST-901 High Precision Large Current Generator use ARM chip to control the output process and large capacity of toroidal transformer, and equipped with LCD screen display current meter, also showed primary current value, second current value, turn ratio and the action time. Equipped with aluminum alloy chassis, PC panel, which has the advantages of beautiful appearance, large output capacity, small volume, light weight etc. High Precision Large Current Generator is mainly applied to test CT turn ratio in the power system and the contact resistance etc, which need large current.
Main Specifications
1. Power Supply: AC 220V± 10%· 25A, 50Hz/60Hz
2. Current Output: AC: 1000A· 5V or 500A· 10V, Capacity: 5KVA
3. The current output waveform distortion: ≤ 5%
4. Display, primary current, second current and turn ratio,
Accuracy: ± 0.5%,
Primary current range: 0-1100A, Resolution: 0.1A;
Measurement secondary current range: 0-6A, Resolution: 0.001A
Current Duration:
1000A range: 1000A 2-3minutes,
500A range: 3-6minutes
500A range: 500A 2-3minutes,
5. Dual protection (overload electronic protection and software protection)
6. Working environment: Temperature -10~40° C, relative humidity≤ 80%
7. Dimension: 430mm× 260mm× 260mm
8. Weight: 28Kg
Product Groups