• Gf302 Portable Multifunction Power Meter Calibrator, Test and Measuring Instruments
  • Gf302 Portable Multifunction Power Meter Calibrator, Test and Measuring Instruments
  • Gf302 Portable Multifunction Power Meter Calibrator, Test and Measuring Instruments
  • Gf302 Portable Multifunction Power Meter Calibrator, Test and Measuring Instruments
  • Gf302 Portable Multifunction Power Meter Calibrator, Test and Measuring Instruments
  • Gf302 Portable Multifunction Power Meter Calibrator, Test and Measuring Instruments

Gf302 Portable Multifunction Power Meter Calibrator, Test and Measuring Instruments

After-sales Service: 24 Hours Service
Warranty: 3 Years
Application: Chemical Instrument, Mechanical Instrument, Electromagnetic Instrument
Certification: CE, CCC
LCD Display: With LCD Display
Customized: Customized
Customization:
Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
GF302
Stability
0.01%/Min
Weight
20kg
Size
460X430X185mm
Relative Humidity
Less Than 85%
Display
8inch LCD Display
Communication Port
RS232 Interface
Adjustment Range
-1~0~1
Load Capacity
25va
Frequency
50/60Hz
Transport Package
Standard Export Carton
Specification
CE, ISO9001: 2008, IEC
Trademark
GFUVE
Origin
Beijing, China
Production Capacity
80PCS/Month

Product Description

Application of Digital calibration device
GF302 portable multifunction instrument Calibrator ,CE,ISO approved,Test and measuring instruments


GF302 portable multifunction instrument Calibratoris suitable for power plant and power grid companies measuring and testing department and instrumentation classes, and national levels measuring and testing institutions, railway, petroleum, chemical industry and other large industrial and mining enterprises, scientific research units, etc.

 
Gf302 Portable Multifunction Power Meter Calibrator, Test and Measuring Instruments
Gf302 Portable Multifunction Power Meter Calibrator, Test and Measuring Instruments
Gf302 Portable Multifunction Power Meter Calibrator, Test and Measuring Instruments



Introduction

This device is according to nation verification regulation JJG124-2005 "ammeter, voltmeter, power table and resistance meter calibration regulations, JJG126-95" AC power transformation for DC power electrical measurement transducer calibration regulations, Q/GDW140-2006 "AC sample measuring device travel inspection management rules" and JJG597-2005 "AC electric energy meter verification device" and the relevant countries standard requirements and design three-phase 0.05 magnitude table source integration calibration device.The core technology of the function of device with digital signal processor (DSP) and 16 high-speed digital converter composed of high precision work frequency communication terminal;The signal source of use is DSP and 16 high-speed digital-to-analog converters can control of the sine wave, distortion wave signal source;Equipment has high precision, stable and reliable, and convenient operation, flexible, and other characteristics

Functions and Features
All kinds of electric measurement transducer can be checked, including:AC/DC voltage transducer, AC/DC current transducer, frequency transducer, phase transducer, single/ three-phase AC active power transducer, 3-phase reactive power transducers;
Check all kinds of electric measurement indicating meter, including:AC/DC voltmeter, AC/DC ammeter, frequency meter, phase meter, single three-phase AC active power meter, three-phase AC reactive power meter, synchronous meter, etc.;
To test single-phase, three-phase electronic, mechanical watt-hour meter or energy meter/ kWh meter error;
To calibrate AC sample device, RTU, measurement device error;
The built-in electric measurement transducer, electric measurement instrument and meter instructions of verification procedures, can fully automatic or semi-automatic for verification, can save 1000 group check data;
As a voltage source, a current source and power source for high precision, and it is high stability standard resource;
8'-inch big screen color display;The system is WINDOW XP or embedded system;English interface.
The software calibration, it does not need to open the case, stable and reliable;
Voltage output terminal with short circuit, current output terminal open protection and power amplifier overheating protection function;
With automatic failure detection function, shows fault part, the convenience users check line;
With RS232 interface, it can connect computer for data management.

Technical Data

Electrical parameters
Accuracy class 0.05%, 0.1%
Power supply Single phase AC 220V±10% or 110V±10%, 50/60Hz
Communication port USB, RS232, RS485, LAN
AC Voltage output
Range(U1,U2,U3) 50V, 100V, 200V, 400V, 600V
Adjustment range (0 - 120)% RG
Adjustment resolution 0.01% RG, 0.1% RG, 1% RG, 10% RG
Stability 0.01% /1min
Distortion ≤0.2% (non-capacitive load)
Max. output load 25VA for each phase
Accuracy 0.05% RG
AC Current output
Range(I1,I2,I3) 0.5A, 1A, 2.5A, 5A, 10A, 20A
Adjustment range (0 - 120)% RG
Adjustment resolution 0.01% RG, 0.1% RG, 1% RG, 10% RG
Stability 0.01% /1min
Distortion ≤0.2% (non-capacitive load)
Max. output load 25VA for each phase
Accuracy 0.05% RG
AC Power output
Active output stability 0.01%RG/1min
Reactive output stability 0.02%RG/1min
Active accuracy 0.05% RG
Reactive accuracy 0.1% RG
Frequency  output
Adjustment range 45-65Hz
Adjustment resolution 1Hz, 0.1Hz, 0.01Hz and 0.001Hz
Resolution 0.001Hz
Accuracy 0.002Hz
Power factor output
Adjustment range -1 to 0 to +1
Adjustment resolution 0.0001
Resolution 0.0005
Phase output
Adjustment range 0°-359.999°
Adjustment resolution 10°, 1°, 0.1°, 0.01°
Resolution 0.001°
Accuracy 0.05°
Harmonic configuration
Times 2 to 31
Content 0-40%
Phase 0°-359.999°
Configuration error (10% RD + 0.1%), RD refers to the configuration value of harmonic contents
DC Voltage output
Range 75mV, 75 V, 150 V, 300 V, 500V, 1000 V
Adjustment range (0-120)% RG
Adjustment resolution 0.01% RG, 0.1% RG, 1% RG, 10% RG
Stability 0.01% RG / 1 min
Distorting ≤0.2% (non-capacitive load)
Output load 25VA
Accuracy 0.05% RG
Ripple contents ≤1%
DC Current output
Range 0.5 A,1A, 2.5 A, 5 A, 10A, 20 A
Adjustment range (0-120)% RG
Adjustment resolution 0.01% RG, 0.1% RG, 1% RG, 10% RG
Stability 0.01% RG / 1min
Distortion ≤ 0.2% (non-capacitive load)
Output load 25VA
Accuracy 0.05% RG
Ripple contents ≤1%
Energy Error
Active error 0.05% RG
Reactive error 0.1% RG
DC Input Voltage Measurement
Range 0 to ±20V
Measurement range (0-120)% RG
Accuracy 0.01% RG
Resolution 0.001% RG
DC Input Current Measurement
Range 0-20mA
Measurement range (0-120)% RG
Accuracy 0.01% RG
Resolution 0.001% RG
Mechanical parameters
Dimensions (W×H×D) (mm) 460x430x185
Weight (kg) 20
Environmental conditions
Working temperature 0°C to 40°C