FU-25 Split Core Ring Type Current Transformer
The model FU-25 Split Core Ring Type Current Transformer is suitable for 200A cable online measurement, the user friendly shape make It easily clamp onto cables or bus bars.
Characteristic and application: Avaliable for cable that under 300A online measurement
Diameter of clamping wire: φ 25MM
Overall dimensions: : 57MMx76MMx20MM
Load capacity: ≤ 4Ω
Installation: Suspension, use the screws to tighten the opening
Output mode: Lead output
Technical parameter
Primary currentSecondary currentAccuracy
20A10mA0.2, 0.5
30A30mA0.2, 0.5
30A15mA0.2, 0.5
30A10mA0.2, 0.5
40A40mA0.2, 0.5
40A20mA0.2, 0.5
50A50mA0.2, 0.5
50A25mA0.2, 0.5
60A30mA0.2, 0.5
60A20mA0.2, 0.5
80A40mA0.2, 0.5
100A50mA0.2, 0.5
100A40mA0.2, 0.5
300A150mA0.2, 0.5
Technical parameters |
|
Standards |
IEC/EN60044-1 & IEC61010-1 & IEC61869-2&ANSI C57.13 |
Ratio |
1000: 1, customized |
Nominal input current(Primary current) |
0-300A |
Overload withstand |
1.2 times rated current continuously |
Accuracy |
0.2%, 0.5 %, 1% |
System Voltage |
720V(0.72kV) |
Output signal |
0-300mA
333mV AC or 100mV-2V optional |
Burden |
2.5VA |
Frequency range |
40 Hz....500 Hz |
Dielectric strength |
3KV 50Hz/60Hz at 1 minute |
Output mode |
Terminal output |
Max. jaw opening |
25 mm |
Mechanical parameters |
|
Dimensions (W×D×H) (mm) |
83mm x 129mm x 28 mm |
Weight (g) |
120 |
Operating conditions |
|
Operating temperature |
-25 to +55°C |
Relative Humidity |
0-85% non-condensing |
Altitude |
<3500 meters |
Condition |