• Current Transformer Secondary Output AMP
  • Current Transformer Secondary Output AMP
  • Current Transformer Secondary Output AMP
  • Current Transformer Secondary Output AMP
  • Current Transformer Secondary Output AMP
  • Current Transformer Secondary Output AMP

Current Transformer Secondary Output AMP

Application: Electronic, Instrument, Position Sensor
Type: Current Transformer
Phase: Single
Operation Condition: Indoor
Usage: Protection, Measurement
Winding Form: Single Layer & Tightly Wound Type
Customization:
Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
LZCG930-10
Insulating Medium
Epoxy Resin
Installation
Active Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Primary Current
30-1000A
Overload Withstand
1.2 Times Rated Current Continuously
Key Words
Secondary Output 5 AMP Primary Input
Key Word
Manufacturing of Protection Current Transformer
Model
Leakage Current Transformer
Accuracy
0.2%, 0.5 %, 1%
Rated Voltage
35kv
Output Signal
1A or 5A
Frequency Range
40 Hz-60 Hz
Burden
≤30va
Transport Package
Standard Export Box
Specification
φ 60xφ 155x60
Trademark
GFUVE
Origin
Beijing, China
Production Capacity
500000pieces/Year

Product Description

Product Description
LZCG series Cast Resin Straight-Through Current Transformer is suitable for current measurement and
microcomputer protection of electrical equipment in 10KV and 35KV AC power system. It is widely used in not only compact fully insulated ring network switchgears such as ABB-Safe Ring/Safe Plus, Unstitch, Schneider RM6, SM6, Siemens 8DJ10/8DH10, Simosec, FBX, Fluokit, Omar Garbo GA, GAE; SEL TPS(Q); VEI Unifluorc; Eaton SVS/12 ring network, but also cable distribution boxes because of
its small size, light weight, operable and convenient installation. It is very convenient that the transformer can be directly installed at the inlet and outlet cables.
New magnetic material is taken to be the core of the current transformer, which has high magnetic
permeability, low saturation magnetization and good stability. Therefore, the measuring accuracy is higher
and the instrument security factor is lower. Since the high quality silicon processed by advanced technology is taken to be the core of the protection windings, which assured the accuracy limit factor is higher. The semicircular ring core and secondary windings are vacuum poured by high quality epoxide resin in the fire retardant plastic casing, which has the characteristic of moisture proof, stable performance and dispensing with maintenance.Small size, light weight, small footprint, fixed in the ring network switchgear cable.The cable can cross the current transformer through its internal poles quickly and uniformly. The Cast Resin Straight-Through Current Transformer can be divided several kinds according to the various current ratio, accuracy and rated loads. The specific parameters are showed in the corresponding to each model parameter tables.
Current Transformer Secondary Output AMP
Parameters
Technical parameters  
Standards IEC60044-1; IEC 61869-2; NTC 2205; ANSI C57.13; GB1208-2006
Rated primary current 30-1000A
Rated load ≤30VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS≤10
Mechanical parameters
Dimensions (W×D×H) (mm) φ60×φ155×60
Weight (kg) 3.6
Operating conditions
Operating temperature -35°C to +55°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Altitude <3500 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.
Technical data
Type LZCT722-10 LZCT722-10 LZCT722-10            
Purpose Measuring current transformer Protection current transformer Double winding current transformer            
Rated primary current (AMP) Accuracy class and rated load(VA) Accuracy class and rated load(VA) Composite accuracy class and rated load(VA)            
0.2S 0.2 0.5 10P20 10P15 10P10 0.2S 0.5 10P15 10P10
30     2              
40     2.5              
50     3.75     2        
75   3.75 5   2 3.75        
100 2.5 5 7.5   2.5 3.75        
150 5 7.5 10 2.5 3.75 6.25 2.5 3.75   2.5
200 7.5 10 15 3.75 5 7.5 5 7.5   3.75
300 10 15 20 5 7.5 10 7.5 10 2.5 5
400 15 20 25 6.25 7.5 15 10 12.5 3.75 5
500 20 25 25 6.25 7.5 15 15 15 3.75 5
600 20 30 30 7.5 10 20 15 20 3.75 7.5
SELECTION GUIDE
 Model Primary rated current Rated load Aperture (mm) Description (mm) Weight (kg) Material Water-proof
LZCK-55 100-1500A ≤10VA φ55 180×138×52 2 ABS+Resin  IP65
LMCK185-10 300-3000A ≤25VA φ185 350×283×55 4.5 ABS+Resin  IP65
LZCK310-10 300-600A ≤10VA φ50 φ50 x φ110 x 32 1 Resin silicon case (option)
LZCK322-10 30-600A ≤10VA φ50 φ50 x φ110 x 52 1.6 Resin silicon case (option)
LZCK350-10 20-600A ≤25VA φ50 φ50 x φ110 x 105 3.1 Resin silicon case (option)
LZCK720-10 20-1000A ≤25VA φ60 φ80 x φ110 x 50 2.1 Resin silicon case (option)
LZCK2500-10 500-1500A ≤20VA φ120 φ120 x φ185 x 100 7 Resin silicon case (option)
LZCG530-10 30-600A ≤20VA φ45 φ45 x φ120 x 65 2.1 Resin silicon case (option)
LZCG930-10 100-1500A ≤25VA φ60 φ60 x φ155 x 60 3.6 Resin silicon case (option)
LZCT722-10 20-600A ≤10VA φ82 φ82 x φ130 x 55 2.3 Resin silicon case (option)

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now