• High Voltage Current Transformer Ratio Primary Current Injection Test Set
  • High Voltage Current Transformer Ratio Primary Current Injection Test Set
  • High Voltage Current Transformer Ratio Primary Current Injection Test Set
  • High Voltage Current Transformer Ratio Primary Current Injection Test Set
  • High Voltage Current Transformer Ratio Primary Current Injection Test Set
  • High Voltage Current Transformer Ratio Primary Current Injection Test Set

High Voltage Current Transformer Ratio Primary Current Injection Test Set

Application: Primary Current Injection Test Set
Power: Electricity
Certification: CE, CCC
Current Output: 0-1100A
Customized: Customized
Power Supply: AC:220V, 25A,50Hz/60Hz
Customization:
Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
TEST-901
Current Range
0-1100A
Capacity
5kVA
Second Current
0-6A
Dimension(mm)
430X260mmx260mm
Usage
Auto Testing Machine
Distortion
≤5%
Accuracy
0.5%
Weight of The Machine
28kg
Class
0.5
Transport Package
Standard Export Box
Specification
CE, ISO9001: 2008, IEC
Trademark
GFUVE
Origin
Beijing, China
Production Capacity
100PCS/ Month

Product Description

TEST-901 High voltage current transformer ratio primary current injection test set

High Voltage Current Transformer Ratio Primary Current Injection Test Set
High Voltage Current Transformer Ratio Primary Current Injection Test Set
High Voltage Current Transformer Ratio Primary Current Injection Test Set
Product description

TEST-901 High Precision Large Current Generator use ARM chip to control the output process and large capacity of toroidal transformer, and equipped with LCD screen display current meter, also showed primary current value, second current value, turn ratio and the action time. Equipped with aluminum alloy chassis, PC panel, which has the advantages of beautiful appearance, large output capacity, small volume, light weight etc. High Precision Large Current Generator is mainly applied to test CT turn ratio in the power system and the contact resistance etc, which need large current.
 
Most advanced primary current injection test system to simplify all types of switchgear and CT commissioning, ground grid, circuit breaker testing and more
Modular design to permit optimal user configuration of output current vs. unit size
Compact transport cart facilitates portability into switchgear rooms with limited space
Unique I/30 function allows the current to be pre-set using low current to prevent test sample heating, thus eliminating corruption of test result
This powerful test system is designed for primary injection testing of protective relay equipment and circuit breakers. It is also used to test the turns ratio of current transformers and for other applications that require high variable currents.
Related searches for Primary Current Injection Test Set
primary current injection test
primary current injection test procedure
primary current injection tester
primary injection test equipment
current injection test equipment
current injection testing
primary injection testing procedure
primary injection vs secondary injection
Some results are removed in response to a notice of local law requirement. For more information, please see here.


Main Specifications
 
Electrical parameters
Accuracy ±0.5%
Power Supply(AC) 220V±10%·25A, 50Hz/60Hz or
110V±10%·50A, 50Hz/60Hz
Current Output (AC) 1000A·5V or 500A·10V
Capacity 5KVA
The current output waveform distortion ≤5%
Dual protection overload electronic protection and software protection
Primary current
Range 0-1100A
Resolution 0.1A
Accuracy <0.5%
Secondary measurement
Range 0-6A
Resolution 0.001A
Accuracy <0.5%
Current duration
1000A range 1000A    2-3minutes
500A      3-6minutes
500A range 500A      2-3minutes
Mechanical parameters
Dimensions (W×D×H) (mm) 430×260×260
Weight(kg) 28
Environmental conditions
Temperature -10°C to 40°C
Relative humidity ≤80%
High Voltage Current Transformer Ratio Primary Current Injection Test Set
 

Send your message to this supplier