• Electrical 3000A Primary Current Injection Test Equipment
  • Electrical 3000A Primary Current Injection Test Equipment
  • Electrical 3000A Primary Current Injection Test Equipment
  • Electrical 3000A Primary Current Injection Test Equipment
  • Electrical 3000A Primary Current Injection Test Equipment
  • Electrical 3000A Primary Current Injection Test Equipment

Electrical 3000A Primary Current Injection Test Equipment

After-sales Service: Yes
Warranty: Yes
Accuracy: ±0.5%
Power Supply (AC): 380V·50A, 50Hz/60Hz
Current Output (AC): 3000A·5V or 1500A·10V
Capacity: 15kVA
Customization:
Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
TEST-903
The Current Output Waveform Distortion
≤5%
Range
0-3300A
Resolution
0.1A
Accuracys
<0.5%
Temperature
-10°c to 40°c
Relative Humidity
≤80%
Transport Package
Standard Package
Specification
380x350x360
Trademark
GFUVE
Origin
China
Production Capacity
5000 Pieces/Mes

Product Description

TEST-903 primary current injection test kit adopts ARM chip to control the output process and large capacity of toroidal transformer. It is equipped with LCD screen display current meter, also showed primary current value, secondary current value, turn ratio and the phase shift. Aluminum alloy body with PC panel component the shell.
TEST-903 is mainly applied to test CT turn ratio and polarity in the power system, the contact resistance, high voltage circuit breaker protection test and high voltage generator test etc, which need large current on-site or in the lab.
 
FEATURES:
Permanent current up to 3000 A, 15KVA
Max current output up to 3300A.
Built-in digital ammeter 0.5% accuracy.
Built-in digital timer resolution 1 ms (Optional).
Made up of two units, control and power unit
Thermal and short-circuit protection.
 
Electrical parameters
Accuracy ±0.5%
Power Supply(AC) 380V·50A, 50Hz/60Hz
Current Output (AC) 3000A·5V or 1500A·10V
Capacity 15KVA
The current output waveform distortion ≤5%
Primary current
Range 0-3300A
Resolution 0.1A
Accuracy <0.5%
Secondary measurement
Range 0-6A
Resolution 0.001A
Accuracy <0.5%
Current duration
3000A range 3000A     2-3minutes
1500A      3-6minutes
1500A range 1500A      2-3minutes
With timer
Range 0.0001~999.99S
Resolution 0.001S
Accuracy <0.5%±5 words
Mechanical parameters
Dimensions (W×D×H) (mm) 380×350×360 and 340×290×420
Weight(kg) Control Host 48kg,
External voltage regulator weight 42kg
Environmental conditions
Temperature -10°C to 40°C
Relative humidity ≤80%
Electrical 3000A Primary Current Injection Test Equipment