Find Similar Products

Basic Info.

Model NO.
TEST-901
Power Supply
AC 220V±10%-25A
Frenquency
50Hz/60Hz
Current Output
AC 1000A-5V or 500A-10V
Primary Current Range
0-1100A
Secondary Measurement
0-6A
The Current Output Waveform Distortion
≤5%
Dual Protection
Overload Electronic Protection and Software Protec
Capacity
5kVA
Transport Package
Standard Package
Specification
430× 260× 260
Trademark
GFUVE
Origin
China
Production Capacity
100000 Pieces/Mes

Product Description

TEST-901 Full-automatic CT PT Tester/CT/PT Transformation Ratio Test

TEST-901 primary current injection test set adopts ARM Chip to control its output process and large capacity of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value, second current value, turn ratio and the action time. Packing is used as aluminum alloy body with PC panel. TEST-901 is mainly applied to CT turn ratio testing in the power system and contact resistance test which need large current.
 
Electrical parameters
Accuracy ±0.5%
Power Supply(AC) 220V±10%·25A, 50Hz/60Hz or
110V±10%·50A, 50Hz/60Hz
Current Output (AC) 1000A·5V or 500A·10V
Capacity 5KVA
The current output waveform distortion ≤5%
Dual protection overload electronic protection and software protection
Primary current
Range 0-1100A
Resolution 0.1A
Accuracy <0.5%
Secondary measurement
Range 0-6A
Resolution 0.001A
Accuracy <0.5%
Current duration
1000A range 1000A    2-3minutes
500A      3-6minutes
500A range 500A      2-3minutes
With timer
Range 0.0001~999.99S
Resolution 0.001S
Accuracy <0.5%±5 words
Mechanical parameters
Dimensions (W×D×H) (mm) 430×260×260
Weight(kg) 25
Environmental conditions
Temperature -10°C to 40°C
Relative humidity ≤80%
Full-Automatic CT PT Tester/CT/PT Transformation Ratio Test
Beijing GFUVE Electronics Co., Ltd. was established in 2005. It combined science, industry and trade together as one high-tech enterprise. GFUVE mainly produces high voltage ammeter recorder, IEC61850 test suite software, meter test equipment, reference standard meter, phantom load power source, electrical measurement instrument, relay test set, transformer test, and power analyzer, intelligent digital meter, transducer and current transformer models etc.

Atencion rapida y eficiente todos los dias, incluso festivos. Tambien disponemos de servicio de urgencias para aquellos casos que no puedan esperar mas de media hora en ser solucionados. Atendemos todas las zonas de la pais en todo el mundo.
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier
Product Groups
More