Three Phase Power Quality Analyzer Class a IEC61000-4-30
Contact Supplier
Product Highlights
- Class A Compliance: Fully compliant with IEC 61000-4-30 Class-A standard for rigorous testing.
- High Safety Rating: Rated 600V CAT IV/1000V CAT III for safe service entrance use.
- Portable Design: Lightweight handheld unit (2KG) easy for engineers to carry anywhere.
- Long Battery Life: Up to 7 hours of operating time on a single NiMH battery charge.
- Real-time Analysis: Troubleshoot trends using cursors and zoom tools during background recording.
- Multi-Range Current: Replaceable current clamps (5A-1000A) and flexible probes (up to 6000A).
- Comprehensive Logging: Memory for over 400 parameters with user-defined intervals.
- Direct Line Operation: Operates directly on the line without interrupting the power grid.
Product Attributes
- Customization
- Available
- Warranty
- Three Years
- Measuring Circuit
- 1p2w, 1p3w, 3p3w, 3p4w
- Model NO.
- GF438II
- Keyword
- Portable Power Quality Analyzer Meter
- Measurement Range
- 0-6000V Peak
- Use of The Environment
- 0 ° C to +45 ° C, Humidity 90rh%
- Storage Environment
- -20 ° C to +50 ° C, 95rh% Humidity
- Power Input Voltage
- +100VAC ~ +260VAC
- Battery
- 5000mAh Ni-MH Battery
- Measurement Method
- 10 Waveform (50Hz) The Calculated Frequency
- Display
- Display of a Channel Frequency Value
- Measuring Range / Resolution
- 45.0000Hz-65.0000Hz/0.0001Hz
- Transport Package
- Standard Export Carton
- Specification
- CE, ISO9001: 2008, IEC
- Trademark
- GFUVE
- Origin
- China
- Production Capacity
- 500PCS/Month
Product Images of Three Phase Power Quality Analyzer Class a IEC61000-4-30
Find Similar Products
Product Description
power quality analyzer,CE,ISO9001:2008,IEC approved,english version display,two years quality warranty.
Features
Troubleshoot real-time: Analyze the trends using the cursors and zoom tools-even while background recording continues.
Automatic Transient Mode: Capture 200 kHz waveform data on all phases simultaneously up to 6 kV
Measure all three phases and neutral: With included four current probes
System-Monitor: Up to ten power quality parameters on one screen according to EN50160 power quality standard
View graphs and generate reports: With included analysis software
Logger function: Configure for any test condition with memory for over 400 parameters at user defined intervals.
Mains signaling: Measure interference from ripple control signals at specific frequencies
Inrush mode: For troubleshooting nuisance circuit breaker tripping.
AutoTrend: Every measurement you see is always automatically recorded, without any setup.
Fully Class-A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class-A standard.
Battery Life: Seven hours operating time per charge on NiMH battery pack
High safety rating: 600 V CAT IV/1000 V CAT III rated for use at the service entrance
Comparing to online power quality analyzer, E6000 handheld type with small size, light weight, easy for the engineer to carry and carry out to survey work whenever and wherever.
Easy to wiring
It can operate directly to the line under test under the circumstances that the Power Grid without interrupt.
Multi-range current switching
Based on actual demand, the different range of current clamp can be replaced to improve measurement accuracy.
Applications
Frontline troubleshooting - quickly diagnose problems on-screen to get your operation back online
Predictive maintenance - detect and prevent power quality issues before they cause downtime
Quality of service compliance - validate incoming power quality at the service entrance
Long-term analysis - uncover hard-to-find or intermittent issues
Load studies - verify electrical system capacity before adding loads
Energy assessments - quantify energy consumption before and after improvements to justify energy saving devices.
PARAMETERS
| Name | Measurement type |
|---|---|
| Voltage | rms, ava, pk+, pk-, rms-1/2, CF |
| Frequency | Freq |
| Current | rms, ava, pk+, pk-, rms-1/2, CF |
| Power & energy | P, S, Q, PF, DPF, W |
| Computation | THD, DC, 1-63 Harm, 1-62 InHarm, 1-35 HiHarm, 1-62 SubHarm |
| Voltage harmonic | THD, DC, 1-63 Harm, 0-62 InHarm, 1-35 HiHarm, 1-62 SubHarm , KF |
| Current harmonic | THD, DC, 1-62 Harm |
| Harmonic power | Ia, Ib, Ic, ΣPtotal, ΣQtotal, ΣStotal, 15 minutes |
| Fluctuation and flickering | PST, PLT, Fluct, Fluct Max |
| Unbal | V Pos, A pos , V neg , A neg , V zero, A zero, Unbal |
| Event log | Voltage swell, voltage sags, DIP, surge current, voltage and current distortion out of limit, odd harmonics containing rate out of limited, unbalanced voltage current out of limit, frequency out of limit, PST out of limit, PLT out of limit, long-term voltage interruption, voltage fluctuation deviation, voltage harmonics out of limit, 2-25st harmonicsout of limit |
| P, Q, S name | Measurement type |
| Measurement types | P: Calculate by every 10 cycles S: Calculated by the effective value of voltage and current Q: Calculated by the apparent power, active power |
| Display | Table charts, trend chart |
| Measuring range | According to the range of the voltage and current |
| Resolution | 0.001W |
| Accuracy | ±0.5% |
| Urms | Measurement type |
| Mode | 'Calculated by the square root value of 10/12 cycle |
| Measuring circuit | 1P2W/ 2P3W /3P3W/ 3P4W |
| Basic frequency of the measuring circuit | 50Hz, 60Hz |
| Input channels | 4 phase voltage, 4 phase current |
| Display mode | Effective current value of each channel |
| Range | 120V, 230V, 400V, 1000V, Max 1000V instantaneous voltage |
| Resolution | 0.001V |
| Accuracy | 0.1% RG |
| Arms | Measurement type |
| Mode | 'Calculated by the square root value of 10/12 cycle |
| Display mode | Effective current value of each channel |
| Range | Current: according to the current clamps Option Current clamps:5A/50A/100A/500A/1000A Flexible Current probe: 1000A/3000A/6000A |
| Resolution | 0.001A |
| Accuracy | 0.1% + accuracy of the current clamps |
| Frequency | Measurement type |
| Measurement mode | Calculate by 10 cycles (50Hz) or (60Hz) |
| Display mode | Measurement by 10 cycles |
| Nominal frequency/resolution | 50.000Hz/0.001Hz or 60.000Hz/0.001Hz |
| Bandwidth measurement | 42.5-57.5Hz or 52.5-67.5Hz |
| Accuracy | ±0.001Hz |
| Half-wave RMS current/voltage | Measurement type |
| Measurement mode | Calculate by every 2 cycles. Each cycle ,1/2 cycle made up of a waveform calculation |
| Measuring range/resolution | Voltage: 120V/0.01V, 230V/0.01V, 400V/0.01V, 1000V/0.01V, Current: According to the current clamps |
| measurement accuracy | ±0.1% |
| Power factor | Measurement type |
| Measurement mode | The ratio of average power to apparent power |
| Display mode | Real-time data showed |
| Measurement range/resolution | -1.000-1.000/0.001 |
| Accuracy | ±0.1% |
| Vfund, Afund, Harmonic power | Measurement type |
| Measurement mode | Meet IEC61000-4-7,Analysis time window is ten cycles |
| Window points | 5120 points |
| Display mode | Form figure, trend charts, histograms |
| Number of measurement | 1-50 Times |
| Measurement accuracy | Vfund >1%: Error<1% Vfund <1%: Error<0.05% Rated Voltage Afund >3%: Error<1% Afund <3%: Error<0.05% Current range |
| InHarm Voltage, InHarm current | Measurement type |
| Measurement mode | Meet IEC61000-4-7, Analysis time window is ten cycles |
| Window points | 5120 points |
| Display mode | Form figure, trend charts, histograms |
| Numbers of measurement | 1-16 groups |
| Measurement accuracy | Vfund >1%: Error<1% Vfund <1%: Error<0.05% Rated Voltage Afund >3%: Error<1% Afund <3%: Error<0.05% Current range |
| HiHarm Voltage, HiHarm current | Measurement type |
| Measurement mode | Meet IEC61000-4-7, Analysis time window is ten cycles |
| Window points | 5120 points every 10 cycles |
| Display mode | Form figure, trend charts, histograms |
| Numbers of measurement | 1-35 groups/2100Hz-8900Hz |
| Measurement accuracy | Vfund >1%: Error<1% Vfund <1%: Error<0.05% Rated Voltage Afund >3%: Error<1% Afund <3%: Error<0.05% Current range |
| Voltage/current Unbal (pos, neg) | Measurement type |
| Measurement mode | 3P3W or 3P4W, using three phase of fundamental wave components to calculate |
| Display mode | Form figure, trend charts, histograms |
| Measurement accuracy | Voltage unbal: ±0.2% Current unbal: ±0.5% |
| Voltage fluctuation | Measurement type |
| Measurement mode | Calculate by the quadratic mean of half wave |
| Display mode | Form figure, trend charts |
| Measurement accuracy | ±1% |
| IEC Flickering | Measurement type |
| Measurement | P short term (Pst) , P long term (Plt) |
| Measurement mode | According to IEC61000-4-15 Standard to calculate Pst (10 mins) Plt (2 hours) |
| Display mode | Form figure, trend charts |
| Measurement range | 0-20 |
| Measurement accuracy | ±5% |
| Surge current | Measurement type |
| Measurement mode | Half-wave RMS of current is higher than set value and sustain time is 10ms-1min |
| Display mode | Maximum of the surge current and surge current wave |
| Measurement accuracy | 0.1% |
| Voltage swell, Voltage sags, DIP | Measurement type |
| Measurement mode | Swell: When half-wave RMS of voltage is higher than set value and sustain time is 10ms-1min, judged as swell. Sags: When half-wave RMS of voltage is lower than set value and sustain time is 10ms-1min, judged as sags. DIP: half-wave RMS of voltage is higher than set value and sustain time is 10ms-1min, judged as DIP |
| Display mode | Swell, sags, DIP wave sustain time, extent and so on. |
| Measurement accuracy | 0.1% |
| Machinery | |
| Size | 263mm x 168mm x 65mm |
| Key | 21PCS |
| Binary | binary input:1 ; binary output:1 |
| Comunication Port | USB, 10/100M port |
| Weight | 2KG |
| Power supply | |
| Voltage input | 110V-240V |
| Adapter outpu | 15V, 3A |
| Battery | Rechargeable nickel metal hydride, 5500mAh |
| Battery working time | ≥ 6h |
| Battery recharging time | 5h (Environment temperature 25°C) |
| Power saving facility | LCD backlight brightness is adjustable, standby time is adjustable |
| Display | |
| Size | 112.8 x 84.6mm |
| Color | 260000 color |
| Resolutions | 640 x 480 |
| Brightness | Max 350 cd/m2 (Typ), brightness is adjustable |
| Contrast | 500:1 (Typ) |
| Visual angle | 70/70/50/70 (Typ.)(CR ≥10) ( Left/ Right/ UP/Down) |
| Environment | |
| Working environment | 0°C to +45°C, humidity below 90rh% |
| Storing environment | '-20°C to +50°C, humidity below 95rh% (non-condensing) |
| Store | |
| Type | TF card (inbuilt) |
| Size | 32G |
| Standards | |
| Measurement method | IEC 61000-4-30 |
| Measurement performance | IEC 61000-4-30 A LVL |
| Flickering | IEC 61000-4-15 |
| Harmonic | IEC 61000-4-7 |
| Safety | |
| Standard | GB 4793.1-2007/IEC 61010-1:2001: "Measurement, control and laboratory electrical equipment safety requirements", first part: general requirements. Security level: CAT III 1000 V/ CAT IV 600 V./td> |
| MAX voltage of phase angle input | CAT III 1000V/CAT IV 600V |
Photo

About the Supplier
Company Profile
Beijing GFUVE Electronics Co., Ltd. Was established in 2005. It combined science, industry and trade together as one high-tech enterprise. GFUVE mainly produces split core current transformer, high voltage ammeter recorder, IEC61850 test suite software, meter test equipment, current probe, reference standard meter, phantom load power source, electrical measurement instrument, relay test set, transformer test, CT analyzer, Test equipment, and power meter, power analyzer, intelligent digital meter, transducer, handheld terminal and split core current transformer, voltage transformer and current transformer models etc.
GFUVE is a leader manufacturer of energy meter test products and high voltage ammeter recorder in China. It is professional in energy meter test system, energy meter portable tester and related accessory of current probe. The product of high voltage ammeter recorder develops very quickly in the market. Our company has achieved certification to ISO9001. The products are sold to over 30 provinces in China and exported to overseas including South America, Middle East, South east and Africa.
We have been contributing ourselves to developing the durable and stable products for the usage of the power system. Contact us now for further business relationship. We are here to provide you the best service.
About Our Factory & Business Background
- Address
- Bldg. 2-1111, Joy Mansion, No. 99 Chaoyang North Road, Chaoyang District, Beijing, China
- Terms of Payment
- LC, T/T, PayPal, Western Union
- International Commercial Terms(Incoterms)
- FOB, CIF, FCA, EXW
- Average Lead Time
-
Peak Season Lead Time: one month
Off Season Lead Time: within 15 workdays - Nearest Port
- TIANJING
Our Production Capability & Technical Expertise
Our Industry Experience & Global Business Record
- Export Year
- 2010-08-01
- Main Markets
- North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe
FAQ
- What is the warranty period?
- The product comes with a two-year quality warranty.
- Does the device comply with international standards?
- Yes, it is fully Class-A compliant with IEC 61000-4-30 and meets IEC 61000-4-15 for flickering.
- How long does the battery last?
- The rechargeable NiMH battery provides at least 6 hours of operation, with up to 7 hours per charge.
- Can the current measurement range be adjusted?
- Yes, different current clamps can be replaced based on demand, ranging from 5A to 1000A, with flexible probes up to 6000A.
- Is the device suitable for portable use?
- Yes, it is a lightweight handheld unit weighing 2KG, designed for easy carrying and on-site surveys.
- What safety ratings does the analyzer have?
- It has a high safety rating of 600V CAT IV and 1000V CAT III for use at the service entrance.
- Does it support direct connection to the power line?
- Yes, it can operate directly on the line under test without interrupting the power grid.
- What is the maximum voltage it can measure?
- The measuring range goes up to 6000V Peak, with a maximum instantaneous voltage of 1000V.
Send your message to this supplier
People who viewed this also viewed
-
US$9,999.00 / Piece
-
US$6,500.00 / Set
-
Negotiable
Find Similar Products By Category
- Supplier Homepage
- Products
- Power quality analyzer
- Power quality analyser
- Three Phase Power Quality Analyzer Class a IEC61000-4-30
Related Categories
Hot Searches
- Power Instrument Factories
- Power Energy Meter Factories
- Digital Power Meter Factories
- Power Measuring Factories
- Power Analyzer
- Analyzer Portable
- Quality Control Analyzer
- Energy Analyzer
- Electric Power Analyzer
- Power Quality Analyzer Bulkbuy