GF106T is mainly used for field testing of Protection class CT and PT. This current transformer tester of test items mainly include excitation characteristic, transformation ratio, polarity, degauss, ratio & phase error, 5% and 10% error curves, secondary winding resistance check, withstand test of power frequency alternating current and secondary load. Adopting LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to download data, with simple and convenient operation.









| Electrical parameters | ||
| Accuracy | 0.2%, 0.5% | |
| Power supply | AC 220V±10% or AC 110V±10%, 50/60Hz | |
| Excitation voltage output | 0-2500Vrms | |
| Excitation current output | 0-5Arms (20A peak-value) | |
| Large current output | 0-1000A | |
| Large current cable length | 4m, 95mm² | |
| Accuracy | ≤0.2% | |
| Frequency | 50Hz or 60Hz optional | |
| Secondary winding DC resistance measurement | Range | 0.1-300Ω |
| Accuracy | ≤0.2% | |
| Secondary actual load measurement | Range | 0.1VA-1000VA |
| Accuracy | ≤0.2% | |
| CT/PT phase error measurement | Accuracy | ±4min |
| Resolution | 0.01min | |
| CT ratio error measurement | Range | ≤25000A/5A(5000A/1A) |
| Accuracy | ≤0.2% | |
| PT ratio error measurement | Range | 1-500KV |
| Accuracy | ≤0.2% | |
| LCD display | 5.6' inch blacklight LCD | |
| Cable Length | Primary 5m; Secondary 5m; others customized | |
| Communication port | USB | |
| PC control software | Yes, Optional | |
| Printer | Yes, Thermal printer | |
| Standards | ||
| Reference standards | GB1207-2006, GB1208-2006, GB16847-1997 IEC60044-1, IEC60044-6, IEC61869-1,2,3, ANSI/IEEE C57.13 |
|
| Safety standards | GB 4793.1-2007 | |
| EMC | EMC standard 89/336/EEC FCC Subpart B of Part 15 Class A IEC 1000-4-2/3/4/6 |
|
| Mechanical parameters | ||
| Overall dimension (L x W x H) (mm) | 400 x 250 x 250 | |
| Weight (kg) | ≤22 | |
| Environmental conditions | ||
| Operating Temperature | -10°C to 50°C | |
| Storage Temperature | -40°C to 70°C | |
| Relative humidity | ≤95%,on-condensing | |
| Altitude | ≤2000m | |
| I. Current Transformer (CT) | II. Voltage Transformer (PT) |
| 1. Magnetization curve | 1. Excitation characteristic test |
| 2. Transformation ratio test | 2. Transformation ratio test |
| 3. Polarity | 3. Polarity |
| 4. 5% and 10% error curve | 4. Withstand test of power frequency alternating current |
| 5. Current Injecting(Optional) | 5. Degauss |
| 6. Degauss | 6. Ratio error, phase error |
| 7. Ratio error, phase error | 7. Calculation of knee point value |
| 8. Withstand test of power frequency AC | 8. Actual secondary load test(Burden test) |
| 9. Auto calculation of excitation knee point value | 9. Resistance test |
| 10. Actual secondary load test(Burden test) | |
| 11. Resistance test | |

GFUVE GROUP was established in 2005. It is a high-tech enterprise group company integrating design, production, manufacturing and sales. GFUVE GROUP have five subsidiary and one Technology R & D center. GFUVE mainly produces energy meter test equipment, CT PT analyzer, relay tester, three phase standard power source, reference energy meter, electrical calibrator, power quality analyzer, Power transformer test equipment, circuit breaker tester, high voltage ammeter recorder, High voltage test set, EV & Recharging testing equipment, substation IEC61850 test software, intelligent digital power meter and transducer, current probe & current sensor, split core ct, instrument current transformer & voltage transformer, micro ct & pt, energy meter relay parts and handheld terminal etc.
GFUVE GROUP is a leader manufacturer of energy meter test products, CT PT analyzer, relay tester and high voltage ammeter recorder in China. It is professional in energy meter test system, energy meter portable tester and related accessory. The product of high voltage ammeter recorder develops very quickly in the market. GFUVE GROUP has achieved certification to ISO9001. The products are sold to over 30 provinces in China and exported to overseas including South America, USA, Middle East, Southeast Asia and Africa.