Application: Instrument
Type: Current Transformer
Phase: Single
Operation Condition: Outdoor
Usage: Protection, Measurement
Winding Form: Single Layer & Tightly Wound Type
Customization:
Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
LZCK322-10
Insulating Medium
Epoxy Resin
Installation
Active Type
Magnetic Circuit Structure
Combined Type
Voltage Transformation Principle
Electromagnetic Type
Standards
IEC60044-1; IEC 61869-2; Ntc 2205; GB1208-2006; an
Key Word
Current Transformer
Accuracy Class
0.5s, 0.5%, 1%, 3%
Range of Primary Rated Current
30-600A
Rated Frequency
50/60Hz
Rated Secondary Current
5A or 1A
Instrument Security Factor
Fs≤10
Aperture (mm)
Φ55
Rated Load
≤10va
Weight (Kg)
1.6
Transport Package
Standard Package
Specification
φ 50xφ 110x52
Trademark
GFUVE
Origin
China
Production Capacity
100000 Pieces/Mes

Product Description


LZCK322-10 Medium voltage measurement and 5P10 Protection Clamp Current Transformer 5A

Descripción del producto

LZCK series split core current transformer is suitable for current measurement and microcomputer protection of electrical equipment in 10KV and 35KV AC power system. It is widely used in compact fully insulated ring network switchgears such as ABB-SafeRing/SafePlus...and cable distribution boxes. The transformer can be directly installed at the inlet and outlet cables.The slice is imported silicon material. The semicircular ring core and secondary windings are vacuum poured by insulated resin.
 

PARAMETERS

Technical parameters
Standards IEC60044-1; IEC 61869-2; ANSI C57.13; NTC 2205; GB1208-2006
Rated primary current 30-600A
Rated load ≤10VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS≤10
Mechanical parameters
Dimensions (W×D×H) (mm) φ50xφ110x52
Weight (kg) 1.6
Operating conditions
Operating temperature -35°C to +55°C
Daily average temp <+40°C
Altitude <3500 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

TECHNICAL DATA

Type LZCK322-10 LZCK322-10
Purpose Measuring current transformer Protection current transformer
Ratio Accuracy class and rated load(VA) Accuracy class and rated load(VA)
I1/I2 0.5 1 3 10P15 10P10 10P5
30/1   1 1.5      
50/1   1 2     1.25
75/1   1.5 2.5   1 2
100/1 2 2.5 3   1.5 2.5
200/1 2.5     1.25 2.5  
300/1 3.75     1.25 2.5  
400/1 7.5     1.25 2.5  
500/1 10     1.25 3  
600/1 10     1.5 3  
50/5     2.5      
75/5     2.5      
100/5 2.5          
200/5 3.75          
300/5 5          
400/5 7.5       2.5  
500/5 7.5       2.5  
600/5 10       3.75  

SELECTION GUIDE

 Model Primary rated current Rated load Aperture (mm) Description (mm) Weight (kg) Material Water-proof
LZCK-55 100-1500A ≤10VA φ55 180×138×52 2 PC  IP65
LMCK185-10 300-3000A ≤25VA φ185 350×283×55 4.5 PC  IP65
LZCK310-10 300-600A ≤10VA φ50 φ50 x φ110 x 32 1 Resin silicon case (option)
LZCK322-10 30-600A ≤10VA φ50 φ50 x φ110 x 52 1.6 Resin silicon case (option)
LZCK350-10 20-600A ≤25VA φ50 φ50 x φ110 x 105 3.1 Resin silicon case (option)
LZCG530-10 30-600A ≤20VA φ45 φ45 x φ120 x 65 2.1 Resin silicon case (option)


Selection guide
Modelo Rango de corriente nominal primaria Rango de carga nominal Apertura (mm) Descripción (mm) Peso (kg)
LVZCK-36 100-600A  ≤10VA Φ36  128×120×84 1.2
LZCK-36  100-1000A  ≤10VA Φ36 128×120×84 1.5
LZCK-55  100-1250A  ≤10VA Φ55 180×138×52 2
LMCK185-10  300-5000A  ≤25VA Φ185  350×283×55 4.5

SERVICIO RAPIDO
Atencion rapida y eficiente todos los dias, incluso festivos. Tambien disponemos de servicio de urgencias para aquellos casos que no puedan esperar mas de media hora en ser solucionados. Atendemos todas las zonas de la pais en todo el mundo.
 
Medium Voltage Measurement and 5p10 Protection Clamp Current Transformer 5A
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now