Customization: | Available |
---|---|
Application: | Power, Electronic, Instrument |
Phase: | Single |
Still deciding? Get samples of US$ 3/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
LZCK322-10 Germany Cable Type Split Current Transformers |
Technical parameters | |
---|---|
Standards | IEC60044-1; IEC 61869-2; ANSI C57.13; NTC 2205; GB1208-2006 |
Rated primary current | 30-600A |
Rated load | ≤10VA |
Rated frequency | 50Hz or 60Hz |
Rated secondary current | 5A or 1A |
Rated short-time thermal current | 40kA, 1S |
Rated continuous thermal current | 120%I1n |
Secondary winding power-frequency voltage | 3kV, 1min |
Instrument security factor | FS≤10 |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | φ50xφ110x52 |
Weight (kg) | 1.6 |
Operating conditions | |
Operating temperature | -35°C to +55°C |
Daily average temp | <+40°C |
Altitude | <3500 meters |
Condition | No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current. |
Type | LZCK322-10 | LZCK322-10 Protection current transformer Accuracy class and rated load(VA) |
||||
---|---|---|---|---|---|---|
Purpose | Measuring current transformer | |||||
Ratio | Accuracy class and rated load(VA) | |||||
I1/I2 | 0.5 | 1 | 3 | 10P15 | 10P10 | 10P5 |
30/1 | 1 | 1.5 | ||||
50/1 | 1 | 2 | 1.25 | |||
75/1 | 1.5 | 2.5 | 1 | 2 | ||
100/1 | 2 | 2.5 | 3 | 1.5 | 2.5 | |
200/1 | 2.5 | 1.25 | 2.5 | |||
300/1 | 3.75 | 1.25 | 2.5 | |||
400/1 | 7.5 | 1.25 | 2.5 | |||
500/1 | 10 | 1.25 | 3 | |||
600/1 | 10 | 1.5 | 3 | |||
50/5 | 2.5 | |||||
75/5 | 2.5 | |||||
100/5 | 2.5 | |||||
200/5 | 3.75 | |||||
300/5 | 5 | |||||
400/5 | 7.5 | 2.5 | ||||
500/5 | 7.5 | 2.5 | ||||
600/5 | 10 | 3.75 |