Customization: | Available |
---|---|
Power Supply: | AC 220V or 110V, 50/60Hz |
Test Channels: | 12 Channels with 25V |
Still deciding? Get samples of US$ 15000/Set
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Electrical parameters | ||
Power supply | Single phase AC 220V±10% or 110V±10%, 50/60HzAC | |
Immunity | withstand the 550KV electrostatic environment | |
Test channels | 12 channels with 25V,the current is 50mA | |
Transducer | one analog transducer | |
TIME | Recording time length | 0~9.9s |
Time accuracy | ±0.l%reading ± 2 LSB | |
Resolution | 0.1ms | |
Motion | Ranges | 0~1000mm |
Accuracy | ±1% reading ±1LSB | |
Resolution | 0.1mm | |
Velocity | Ranges | 0~20.00m/s |
Accuracy | ±1%reading ±1LSB | |
Resolution | 0.01m/s | |
DC POWER | Ranges | 15~260V |
Max current | 20A | |
Accuracy | ±1%reading ±1LSB | |
Load change | ≤1% | |
TRIGGER | Voltage | 15~260V |
Current | 0.1-20A | |
Transducer | the transducer states changes | |
Channels | channels states changed | |
Memory | SD card of 2GB,the maximum storage ability is 100 test results. | |
LCD | 5.7″black and white LCD display (320 x 240 pixels) | |
Communication | RS232 and USB communication interface | |
Printer | internal installed 58mm wide thermal printer. | |
Standard | DL/T846.3-2004, IEC61010-1, IEC61326-1 | |
Mechanical parameters | ||
Dimension (L×W×H) (mm) | 380x262x120 | |
Weight (kg) | 6 | |
Environmental conditions | ||
Operating temperature | -10°C to 50°C | |
Storage temperature | -20°C to 70°C | |
Relative humidity | ≤95%RH |