Full Automatic Transformer Tester with Printer

Product Details
Customization: Available
Type: Universal Testing Machine
Accuracy Grade: 0.2%, 0.5%
Diamond Member Since 2013

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
5000000 RMB
Plant Area
>2000 square meters
  • Full Automatic Transformer Tester with Printer
  • Full Automatic Transformer Tester with Printer
  • Full Automatic Transformer Tester with Printer
  • Full Automatic Transformer Tester with Printer
  • Full Automatic Transformer Tester with Printer
  • Full Automatic Transformer Tester with Printer
Find Similar Products

Basic Info.

Model NO.
GF106T
Display
Digital
Control
Computer Control
Weight
22kg
Power Source
AC 220V or 110V
Accuracy
0.2%, 0.5%
Power Supply
AC 220V±10% or AC 110V±10%, 50/60Hz
Large Current Output
0-1000A
Secondary Winding DC Resistance Measurem
0.1-300Ω
Secondary Actual Load Measurement
5va-1000va
CT/PT Phase Error Measurement
±4min
CT Ratio Error Measurement
≤25000A/5A(5000A/1A)
PT Ratio Error Measurement
1-500kv
Reference Standards
GB1207-2006, GB1208-2006, GB16847-1997 IEC60044-1
Relative Humidity
90rh%
Operating Temperature
-10°c to +40°c
Altitude
1000m
Transport Package
Standard Export Box
Specification
400 x 250 x 250
Trademark
GFUVE
Origin
Beijing China
Production Capacity
200sets/Year

Product Description

GF106T class 0.05 1000A 2500V Full-automatic portable ct current transformer tester
GF106T current transformer tester is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopting LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.

Full Automatic Transformer Tester with Printer

MAIN FUNCTIONS
I. Current Transformer (CT) II. Voltage Transformer (PT)
1. Magnetization curve 1. Excitation characteristic test
2. Transformation ratio test 2. Transformation ratio test
3. Polarity 3. Polarity
4. 5% and 10% error curve 4. Withstand test of power frequency alternating current
5. Current Injecting 5. Degauss
6. Degauss 6. Calculation of knee point value
7. Withstand test of power frequency alternating current 7. Actual secondary load test
8. Automatic calculation of excitation knee
point value
8. Resistance test
9. Actual secondary load test
10. Resistance test
PARAMETERS
Electrical parameters
Accuracy 0.2%, 0.5%
Power supply AC 220V±10% or AC 110V±10%, 50/60Hz
Excitation voltage output 0-2500Vrms,
Excitation current output 0-5Arms (20A peak-value)
Large current output 0-1000A
Electrical parameters - continued
Accuracy ≤0.5% (0.2%RD+0.3%RG)
Secondary winding DC resistance measurement Range 0.1-300Ω
Accuracy ≤0.5% (0.2%RD+0.3%RG)
Secondary actual load measurement Range 5VA-1000VA
Accuracy ≤0.5% (0.2%RD+0.3%RG)±0.1VA
CT/PT phase error measurement Accuracy ±4min
Resolution 0.01min
CT ratio error measurement Range ≤25000A/5A(5000A/1A)
Accuracy ≤0.5%
PT ratio error measurement Range 1-500KV
Accuracy ≤0.5%
Standards
Reference standards GB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2-2012
Safety standards GB 4793.1-2007
EMC EMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters
Overall dimension (L x W x H) (mm) 400 x 250 x 250
Weight (kg) ≤22
Environmental conditions
Relative humidity 90RH%
Operating temperature -10°C to +40°C
Altitude ≤1000m