Gfuve Test-901 Large Current Primary Current Injection Test Set
Contact Supplier
Product Highlights
- Powerful Current Output: Max output up to 1100A with 5KVA capacity for large current tests.
- Portable & Lightweight: Compact design weighing 25kg, ideal for on-site testing.
- Advanced Control System: ARM chip control with LCD display and built-in digital timer.
- Dual Protection System: Equipped with electronic and software protection against overload.
- Versatile Applications: Suitable for CT ratio, relay, and circuit breaker testing.
- Long Duration Support: Supports 1000A for 2-3 minutes and 500A for 3-6 minutes.
- Standard Compliance: Meets IEC61010-1 and IEC 61326-1 safety standards.
Product Attributes
- Customization
- Available
- Certification
- CCC
- Protection
- Corrosion Resistance
- Model NO.
- Test-901
- Installation
- Hanging
- Housing
- UPR
- Accuracy
- ±0.5%
- Capacity
- 5kVA
- Communication Port
- RS232
- Transport Package
- Wooden Box
- Specification
- Phasor checker: 187×119×48mm Detector
- Trademark
- GFUVE
- Origin
- Beijing
- HS Code
- 9107000000
- Production Capacity
- 1000
Product Images of Gfuve Test-901 Large Current Primary Current Injection Test Set
Find Similar Products
Product Description
TEST-9011000A PRIMARY CURRENT INJECTION TEST SET
TEST-901 primary current injection test set adopts ARM Chip to control its output process and large capacity of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value, second current value, turn ratio and the action time of circuit breaker. Packing is used as aluminum alloy body with PC panel. TEST-901 is mainly applied to CT turn ratio testing in the power system and contact resistance test which need large current. This model current injection test set is ideal for 1. performance and turn-ratio tests of current transformers; 2. primary tests of protective relays; 3. current tests on low-voltage and high-voltage circuit breakers; 4.commissioning tests that require variable currents










FEATURES
Portable designed
Quick and easy to use
With CT ratio test function
With 6m large current cable
Max current output up to 1100A
Built-in digital timer resolution 1ms
Built-in digital ammeter 0.5% accuracy
Permanent current up to 1000 A, 5KVA
Small size, light weight, easy to test on-site
Thermal and short-circuit & overload protection
APPLICATION
Switchgear Testing
Ground Grid Testing
Primary injection tests
Circuit Breaker Testing
Protective Relay Testing
Current Transformer Testing
Recloser and Sectionalizers
PARAMETERS
| Electrical parameters | |
|---|---|
| Accuracy | ±0.5% |
| Power Supply(AC) | 220V±10%·25A, 50Hz/60Hz or 110V±10%·50A, 50Hz/60Hz |
| Current Output (AC) | 1000A·5V or 500A·10V |
| Capacity | 5KVA |
| The current output waveform distortion | ≤5% |
| Dual protection | overload electronic protection and software protection |
| Primary current | |
| Range | 0-1100A |
| Resolution | 0.1A |
| Accuracy | <0.5% |
| Secondary measurement | |
| Range | 0-6A |
| Resolution | 0.001A |
| Accuracy | <0.5% |
| Current duration | |
| 1000A range | 1000A 2-3minutes 500A 3-6minutes |
| 500A range | 500A 2-3minutes |
| Continuous output | 400A |
| With timer | |
| Range | 0.0001~999.999S |
| Resolution | 0.001S |
| Accuracy | <0.2% ±2 words |
| Standard | |
| Standard | IEC61010-1;IEC 61326-1 |
| Communication port | RS232 |
| Cable | length 2x6m, 70mm² |
| Mechanical parameters | |
| Dimensions (W×D×H) (mm) | 430×260×260 |
| Weight(kg) | 25 |
| Environmental conditions | |
| Operating Temperature | -10°C to 50°C |
| Storage Temperature | -40°C to 70°C |
| Relative humidity | ≤95%,on-condensing |
SELECTION GUIDE
| Model | Accuracy | Primary Current | Ammeter(0-6A) | Timer | Power | Injection Current time | Dimension(W×D×H) (mm) | Weight | Remark |
|---|---|---|---|---|---|---|---|---|---|
| TEST-901 | 0.5% | 0-1100A | YES | YES | 5KVA | 1000A: 2-3min; 500A:3-6min |
430×260×260 | 25KG | Integrated structure |
| TEST-902 | 0.5% | 0-2200A | YES | YES | 12KVA | 2000A:2-3min; 1000A:3-6min |
360×300×295 and 320×300×300 | 35KG+15KG | Fission structure |
| TEST-903 | 0.5% | 0-3300A | YES | YES | 15KVA | 3000A: 2-3min; 1500A:3-6min |
380×350×360 and 340×290×420 | 48KG+42KG | Fission structure |
| TEST-905 | 0.5% | 0-5500A | YES | YES | 30KVA | 5000A:2-3min; 2500A:3-6min |
430×430×445 and 550×450×600 | 68KG+55KG | Fission structure |
About the Supplier
Company Profile
Beijing GFUVE Electronics Co., Ltd. Was established in 2005. It combined science, industry and trade together as one high-tech enterprise. GFUVE mainly produces split core current transformer, high voltage ammeter recorder, IEC61850 test suite software, meter test equipment, current probe, reference standard meter, phantom load power source, electrical measurement instrument, relay test set, transformer test, CT analyzer, Test equipment, and power meter, power analyzer, intelligent digital meter, transducer, handheld terminal and split core current transformer, voltage transformer and current transformer models etc.
GFUVE is a leader manufacturer of energy meter test products and high voltage ammeter recorder in China. It is professional in energy meter test system, energy meter portable tester and related accessory of current probe. The product of high voltage ammeter recorder develops very quickly in the market. Our company has achieved certification to ISO9001. The products are sold to over 30 provinces in China and exported to overseas including South America, Middle East, South east and Africa.
We have been contributing ourselves to developing the durable and stable products for the usage of the power system. Contact us now for further business relationship. We are here to provide you the best service.
About Our Factory & Business Background
- Address
- Bldg. 2-1111, Joy Mansion, No. 99 Chaoyang North Road, Chaoyang District, Beijing, China
- Terms of Payment
- LC, T/T, PayPal, Western Union
- International Commercial Terms(Incoterms)
- FOB, CIF, FCA, EXW
- Average Lead Time
-
Peak Season Lead Time: one month
Off Season Lead Time: within 15 workdays - Nearest Port
- TIANJING
Our Production Capability & Technical Expertise
Our Industry Experience & Global Business Record
- Export Year
- 2010-08-01
- Main Markets
- North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe
FAQ
- What is the maximum current output of the TEST-901?
- The maximum primary current output is up to 1100A, with a permanent current of up to 1000A.
- How long can the device sustain maximum current output?
- It can sustain 1000A for 2-3 minutes and 500A for 3-6 minutes.
- What are the main applications for this test set?
- It is ideal for CT turn ratio testing, protective relay primary tests, and circuit breaker current tests.
- Does the device have protection features?
- Yes, it features dual protection including electronic overload protection and software protection.
- What communication port does the device support?
- The device is equipped with an RS232 communication port.
- What standards does the product comply with?
- It complies with Standard IEC61010-1 and IEC 61326-1.
Send your message to this supplier
People who viewed this also viewed
-
Negotiable
-
Negotiable
Find Similar Products By Category
- Supplier Homepage
- Products
- Split Core Current Transformer
- Others Split Core Current Transformer
- Gfuve Test-901 Large Current Primary Current Injection Test Set
Related Categories
Hot Searches
- High Current
- Current Voltage Factories
- Current Control Factories
- Current Protection Factories
- Low Current
- Current Model
- Current Output
- Current Motors
- Current Brands
- 5kVA Capacity Current Injection Tester Bulkbuy