In power transformer Finished product production process, before the new installation of the transformer in operation, according to the national ministry of preventive test procedures, require the operation of transformer turn ratio or voltage ratio test, to check the correctness of the transformer turn ratio tap-changer of transformer whether inter turn short circuit transformer whether can run parallel. T-203 automatic transformer turns ratio tester adopts three-phase power supply output voltage, the test speed Instrument to adopt advanced technology for A/D, wide range range; High speed single chip microcomputer as the core digital processor, the test fast; English menu display, comprehensively improve the humanization and intelligent, instrument optional RS232 serial and USB connect with computer on line, to realize the remote control of the instrument and intelligent analysis of the data A three phase transformation ratio test, the test speed quickly, High accuracy and Perfect protection function.







| Electrical parameters | ||
| Power supply | Single phase AC 220V±10% or 110V±10%, 50/60HzAC | |
| Test power | 1VAC,10VAC,100VAC,160VAC | |
| Data storage | 100 groups | |
| Display precision | 5 Bits, resolution ratio: 0.0001 | |
| 160V testing voltage | Range1 | 0.8-2000:0.05%±2words; |
| Range2 | 2000-4000:0.1%±2words; | |
| Range3 | 4000-10000:0.2%±2words; | |
| Measuring range ratio | Ratio | 0.8-10000 |
| Accuracy | 0.1%±2words; | |
| LCD | 5.7″black and white LCD display | |
| Key | 9PCS | |
| Test Cable | 12m | |
| Calipers | 4pcs (big), 4pcs (small) | |
| Communication | RS232 and USB communication interface | |
| Printer | internal installed 58mm wide thermal printer. | |
| Degree of protection | IP65 | |
| Standard | IEEE C57.152-2013, IEC 60076-1:2011, AS/NZS 60076.1:2014, CIGRE 445, IEC61010-1, IEC61326-1 |
|
| Mechanical parameters | ||
| Dimension (L×W×H) (mm) | 415x320x168 | |
| Weight (kg) | 7 | |
| Environmental conditions | ||
| Operating temperature | -10°C to 50°C | |
| Storage temperature | -20°C to 70°C | |
| Relative humidity | ≤85%RH | |

GFUVE GROUP was established in 2005. It is a high-tech enterprise group company integrating design, production, manufacturing and sales. GFUVE GROUP have five subsidiary and one Technology R & D center. GFUVE mainly produces energy meter test equipment, CT PT analyzer, relay tester, three phase standard power source, reference energy meter, electrical calibrator, power quality analyzer, Power transformer test equipment, circuit breaker tester, high voltage ammeter recorder, High voltage test set, EV & Recharging testing equipment, substation IEC61850 test software, intelligent digital power meter and transducer, current probe & current sensor, split core ct, instrument current transformer & voltage transformer, micro ct & pt, energy meter relay parts and handheld terminal etc.
GFUVE GROUP is a leader manufacturer of energy meter test products, CT PT analyzer, relay tester and high voltage ammeter recorder in China. It is professional in energy meter test system, energy meter portable tester and related accessory. The product of high voltage ammeter recorder develops very quickly in the market. GFUVE GROUP has achieved certification to ISO9001. The products are sold to over 30 provinces in China and exported to overseas including South America, USA, Middle East, Southeast Asia and Africa.