Basic Info.
- Accuracy
- 0.1%
- Current Output (AC)
- 1000A·5V or 500A·10V
- Capacity
- 5kVA
- Range
- 0-1100A
- Resolution
- 0.1A
- with Timer
- 0.0001 to 999.999s
- Standard
- IEC61010-1;IEC 61326-1
- Communication Port
- RS232
- Weight(Kg)
- 12kg
- Cable
- Length 2X6m, 70mm²
- Current Duration
- 1000A 2-3minutes
- Continuous Output
- 400A
- Operating Temperature
- -10°C to 50°C
- Storage Temperature
- -40°C to 70°C
- The Current Output Waveform Distortion
- ≤5%
- Transport Package
- Plywood Box
- Specification
- 455 × 440 × 150mm
- Trademark
- GFUVE
- Origin
- China
- HS Code
- 903033
- Production Capacity
- 5000sets/Year
Product Description
GF102PORTABLE SINGLE PHASE ENERGY METER TEST BENCH
GF102 series portable single phase energy meter test bench used to test 1pc or 3pcs single phase energy meter or AC meter at same time. Adopt mature signal synthetic and power amplifier technology, high precision voltage source and current source output from 120A/600V. Widely used in lab and field, and then as single phase standard source. It is suite for electricity meter manufacturing enterprises, scientific research institutes, metrological service institutions, electric power companies etc.


PARAMETERS
| Electrical parameters | |
|---|---|
| Accuracy class | 0.02%, 0.05%, 0.1% |
| Power supply | One phase AC 85-265V, frequency 50/60Hz. |
| AC voltage output | |
| Range | 57.7V, 100V, 220V, 380V; max 600V |
| Adjustment range | (0-120)%RG(1) |
| Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
| Stability | 0.01%/120s |
| Distortion | 0.1% (Non-capacitive load) |
| Output load | 25VA or 50VA |
| Measuring accuracy | 0.02%RG or 0.05%RG |
| AC current output | |
| Range | 200mA, 1A, 5A, 20A, 100A; max 120A |
| Adjustment range | (0-120)%RG |
| Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
| Stability | <0.01%/120s |
| Distortion | ≤0.1% (Non-capacitive load) |
| Output load | 50VA or 100VA |
| Accuracy | 0.02%RG or 0.05%RG |
| Power output | |
| Active power output stability | <0.01%RG/120s |
| Reactive power output stability | <0.02%RG/120s |
| Active power measuring accuracy | 0.02%RG or 0.05%RG |
| Reactive power measuring accuracy | 0.05%RG or 0.1%RG |
| Phase output | |
| Output adjustment range | 0°-359.999° |
| Output adjustment fineness | 10,1, 0.1, 0.01 as optional. |
| Resolution | 0.01° |
| Accuracy | 0.02° |
| Power factor | |
| Adjustment range | -1 ~ 0 ~ 1 |
| Resolution | 0.0001 |
| Measurement accuracy | 0.0005 |
| Frequency output | |
| Adjustment range | 40Hz-70Hz |
| Output adjustment fineness | 5Hz, 1Hz, 0.1Hz, 0.01Hz as optional. |
| Resolution | 0.001Hz |
| Accuracy | 0.002Hz |
| Voltage/Current/Harmonic setting | |
| Harmonic number | 2-63times |
| Harmonic content | 0-40% |
| Harmonic phase | 0-359.99 |
| Harmonic setting accuracy | (10%±0.1%)RD(2) |
| Power energy measurement error | |
| Active power energy | 0.02%RG or 0.05%RG |
| Reactive power energy | 0.05%RG or 0.1%RG |
| Power pulse output | |
| Power pulse type | Active pulse, reactive pulse |
| Active power pulse output | 5V, 10mA |
| Power pulse input | |
| Energy pulse type | Support active and reactive pulse, the highest frequency power pulse input is 200K. |
| Standard | |
| Standard | IEC62053-21,22,23; IEC60736; ANSI C12.20-2002; JJG 597-2005; JJG596-2012; JJG 1085-2013; JJF 68-2019; DL/T 826-2002; DL/T 1478-2015; DL/T 448-2016 |
| Safety | |
| Isolation protection | IEC61010-1:2001 |
| Measurement category | 300V CAT III, 600V CAT II |
| Degree of protection | IP20 |
| Declaration of conformity | CE & CNAS certified |
| Functions | |
| LCD | 7 inch touch TFT color LCD |
| Communication port | RS232 or USB |
| Programmable | Yes |
| Meter position | 1pc or 3pcs |
| PC control software | Optional |
| Mechanical parameters | |
| Dimensions (W×D×H)(mm) | 455 × 440 × 150 |
| Weight (kg) | 12 |
| Environmental conditions | |
| Ambient temperature | -10°C to +40°°C |
| Relative humidity | 35%-85% |
| (1) RG means range, the same as below; (2) RD means the setted harmonic content, harmonic can be a single output, also multiple output. |
|
Send your message to this supplier
People who viewed this also viewed
Find Similar Products By Category
- Supplier Homepage
- Products
- Circuit Breaker Testing
- Primary injection test system
- GF102 Portable Single Phase Energy Metertest Bench
Related Categories
Hot Searches
More