Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| Warranty: | Three Years |
| Application: | Electromagnetic Instrument |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Electrical parameters | |
|---|---|
| Accuracy class | 0.05%, 0.1% |
| Power supply | One Phase AC 100-265V, frequency 50/60Hz. |
| AC Voltage output | |
| Range(U1,U2,U3) | 57.7V, 100V, 220V, 380V or 69.3V, 120V, 240V, 480V( optional) |
| Adjustment range | (0-120)%RG(1) |
| Adjust fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
| Stability | 0.01%/120s |
| Distortion | 0.3% (Non-capacitive load) |
| Output load | each phase 30VA |
| Measuring accuracy | 0.05%RG |
| AC Current output | |
| Range (I1, I2, I3 ) | 200mA, 1A, 5A, 20A, 100A(optional) |
| Adjustment range | (0-120)%RG |
| Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
| Stability | <0.01%/120s |
| Distortion | ≤0.3% (Non-capacitive load) |
| Output load | 30VA |
| Accuracy | 0.05%RG |
| Power output | |
| Active power output stability | <0.01%RG/120s |
| Reactive power output stability | <0.02%RG/120s |
| Active power measuring accuracy | 0.05%RG |
| Reactive power measuring accuracy | 0.1%RG |
| Phase Output | |
| Output adjustment range | 0°-359.999° |
| Output adjustment fineness | 10, 1, 0.1, 0.01 as optional. |
| Resolution | 0.01° |
| Accuracy | 0.03° |
| Power Factor | |
| Adjustment range | -1 ~ 0 ~ 1 |
| Resolution | 10, 1, 0.1, 0.01 as optional. |
| Measurement accuracy | 0. 0005 |
| Frequency Output | |
| Adjustment range | 40Hz-70Hz |
| Output adjustment fineness | 5Hz, 1Hz, 0.1Hz, 0.01Hz as optional. |
| Resolution | 0.001Hz |
| Accuracy | 0.005Hz |
| Voltage /Current/Harmonic Setting | |
| Harmonic number | 2-51times |
| Harmonic content | 0-40% |
| Harmonic phase | 0-359.99 |
| Harmonic setting accuracy | (10%±0.1%)RD(2) |
| Power Energy Measurement Error | |
| Active power energy | 0.05%RG |
| Reactive power energy | 0.1%RG |
| Power Pulse Output | |
| Power pulse type | active pulse, reactive pulse |
| Active power pulse output | 5V,10mA |
| Power Pulse Input | |
| Energy pulse type | support active and reactive pulse, the highest frequency power pulse input is 180K. |
| Mechanical parameters | |
| Dimensions (W×D×H) (mm) | 495x390x195 |
| Weight (kg) | 15 |
| Environmental conditions | |
| Ambient temperature | -10°C to +50°C |
| Relative humidity | 35%-85% |
| (1) RG means range, the same as below; (2) RD means the setted harmonic content, harmonic can be a single output, also multiple output. |
|
| No. | Accuracy | Voltage range | Current range | Weight |
|---|---|---|---|---|
| 302D112001 | 0.10% | 0-500V | 0-120A | 22KG |
| 302D1120005 | 0.05% | 0-500V | 0-120A | 22KG |
| 302D11201 | 0.10% | 0-500V | 0-12A | 15KG |
| 302D112005 | 0.05% | 0-500V | 0-12A | 15KG |
| 302D12401 | 0.10% | 0-500V | 0-24A | 16KG |
| 302D124005 | 0.05% | 0-500V | 0-24A | 16KG |