AC current output | Phase current output (effective value) 3×0~30A Maximum output power 260VA/phase Maximum parallel current output (effective value) 0~90A Long-term allowable working value of phase current (effective value) >10A Allowable working time of maximum current >11s Accuracy <±0.2% |
AC voltage output | Phase voltage output (effective value) 5×0~130V Line voltage output (effective value) 0~260V Maximum output power 70VA/phase Accuracy <±0.2% |
DC voltage output | Output range 0~300V or 5×0~±130V Maximum output power 130VA Accuracy <±0.2% |
DC current output | Output range -10~10A or 3×0~±10A Maximum output power 200VA Accuracy <±0.2% |
Binary input | Idle contact 1~20mA, 24V (DC) Electric potential contact 0~250V (DC) |
Binary output | Idle contact 250V/0.5A (DC) |
Rated output | Frequency error <±0.01HzHz Phase error <±0. 2° Waveform distortion <±0.3% (fundamental wave) Time error <40µs Output frequency 0~1050Hz Superposed harmonic wave 0~21times |
Power voltage | Allowable range AC220V±10%, 50/60Hz±10% |
Ambient temperature | Use range 0~45 Storage range -25~70 |
Time measurement | Test range 0.1ms~999999.999s |
Exterior appearance of cabinet | Imported electromagnetic compatible cabinet, which is made of high-grade all aluminum alloy extruded section and has fine appearance, is selected. Dimension of cabinet: length×width×height 360mm×195mm ×375mm |
Weight of cabinet | Weight of host machine 16.6kg |
Load-bearing output | Selectable between light load or heavy load output (When any phase current output surpasses 15A, it is suggested to press key F3 before test of each functional module so as to switch to heavy load output mode) |