Class: 0.2
Operating Temperature: 0 ~ 40°
Dimensions: 55mm X 75mm X 120mm
Frequency: 45--65Hz
Adjust Fineness: 5 X 10-5
Warranty: 2 Years
Samples:
US$ 250/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
FUD-F
Key Word
Frequency Transducer
Output
4-20mA DC
Transport Package
Standard Export Box
Specification
EN 61010-1, CE, ISO9001: 2008, IEC
Trademark
GFUVE
Origin
Beijing, China
Production Capacity
10000PCS/ Month

Product Description


FUD-F MULTIPLE RANGE VARIABLE FREQUENCY TRANSDUCER
Multiple Range Single Phsae AC Variable Frequency Transducer

As the leading product in market, FUD-F multiple range variable frequency transducer adopts SCM as the core with the latest algorithm to achieve precise measurement of frequency in AC circuit.
FUD-F frequency transducer measures Power Frequency over a specified Frequency Range and converts it to an industry standard output signal which is directly proportional to the measured input. These Transducers provide an output which is load independent and isolated from the input. it are used in a variety of Distribution and Transmission Substations, Generation and Industrial applications for measuring various AC power quantities and providing real-time analog signals to drive PLC, SCADA, and driving panel instruments. As the leading product in market, FUD-F multiple range variable frequency transducer adopts SCM as the core with the latest algorithm to achieve precise measurement of frequency in AC circuit.

FEATURES
Frequency transducer
Multiple range frequency transducers
Adopt the SCM as the core technology
With the latest algorithm
Accuracy class can reach 0.1%
 
MODEL DESCRIPTION

FUD-Type-Input-Power Supply-Frequency range-Output
AC input V1: 100V±40%, V2: 220V±40%, V3: 270V±40%,
V4: 400V±40%, V5: User defined.
Power supply P1: AC110V±10%, P2: AC220V±15%
Frequency range F1: 45-55Hz, F2: 48-52Hz, F3: 40-60Hz, Fn: User defined.
DC output O1: 0-5V, O2: 1-5V, O3: 0-20mA, O4: 4-20mA.
Example 1: FUD-F-V2-P2-F1-O4
FUD series frequency transducer Input voltage: AC220±40%
Power: AC220V±15%
F range: 45-55Hz
Output: DC4-20mA
Please check the type, input range, output range and power supply when your order the product.

TECHNICAL INDEX

Technical Index
Standard QB/441600 17 079-2001
Accuracy 0.1%, 0.2%
Consumption ≤3VA
Insulation voltage AC 2kV/min.1mA (Between input- output / power)
Response time ≤300ms
Input range AC100-400V(option),45Hz-60Hz
Absorbed power ≤0.22VA/220V, ≤0.10VA/100V  
Overload 2 times continuous
Load resistance Current output: RL≤650Ω
Voltage output: RL≥2kΩ
Working environment Temperature: -10 to +50ºC
RH: 20-90%, without condensation
Storage conditions Temperature: -40 to +70ºC
RH: 20-95%, without condensation
Installation 35mm DIN sliding-way or M4 screws