| Customization: | Available |
|---|---|
| Application: | Instrument |
| Type: | Current Transformer |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical parameters |
|
|---|---|
| Standards | IEC60044-1; IEC 61869-2; ANSI C57.13; NTC 2205; GB1208-2006 |
| Rated primary current | 30-600A |
| Rated load | ≤20VA |
| Rated frequency | 50Hz or 60Hz |
| Rated secondary current | 5A or 1A |
| Rated short-time thermal current | 40kA, 1S |
| Rated continuous thermal current | 120%I1n |
| Secondary winding power-frequency voltage | 3kV, 1min |
| Instrument security factor | FS≤10 |
| Mechanical parameters | |
| Dimensions (W×D×H) (mm) | φ82xφ130x50 |
| Weight (kg) | 1.5 |
| Operating conditions | |
| Operating temperature | -35°C to +55°C |
| Daily average temp | <+40°C |
| Altitude | <3500 meters |
| Condition | No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current. |
Type |
LZCT723-10 | LZCT723-10 | ||||
|---|---|---|---|---|---|---|
| Purpose | Measuring current transformer | Protection current transformer | ||||
| Ratio | Accuracy class and rated load(VA) | Accuracy class and rated load(VA) | ||||
| I1/I2 | 0.2S | 0.2 | 0.5 | 10P15 | 10P10 | 10P5 |
| 30/1 | 1.5 | 0.5 | ||||
| 50/1 | 1.5 | 1.25 | ||||
| 75/1 | 2 | 1 | 2 | |||
| 100/1 | 2.5 | 1.5 | 2.5 | |||
| 200/1 | 3 | 1.25 | 2.5 | |||
| 300/1 | 2.5 | 3.5 | 1.25 | 2.5 | ||
| 400/1 | 2.5 | 3.5 | 5 | 1.25 | 2.5 | |
| 500/1 | 3.5 | 5 | 7.5 | 1.25 | 3 | |
| 600/1 | 5 | 7.5 | 10 | 1.5 | 3 | |
| 50/5 | 1 | |||||
| 75/5 | 1.5 | 1.5 | ||||
| 100/5 | 2.5 | 2.5 | ||||
| 150/5 | 3.75 | 2.5 | ||||
| 200/5 | 2.5 | 5 | 2.5 | 3.75 | ||
| 300/5 | 2.5 | 3.75 | 7.5 | 2.5 | 6.25 | |
| 400/5 | 5 | 7.5 | 10 | 3.75 | 7.5 | |
| 500/5 | 5 | 7.5 | 10 | 3.75 | 10 | |
| 600/5 | 7.5 | 12.5 | 15 | 3.75 | 10 |