Technical parameters |
|
---|---|
Standards | IEC60044-1; IEC 61869-2; ANSI C57.13; NTC 2205; GB1208-2006 |
Rated primary current | 30-600A |
Rated load | ≤20VA |
Rated frequency | 50Hz or 60Hz |
Rated secondary current | 5A or 1A |
Rated short-time thermal current | 40kA, 1S |
Rated continuous thermal current | 120%I1n |
Secondary winding power-frequency voltage | 3kV, 1min |
Instrument security factor | FS≤10 |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | φ82xφ130x50 |
Weight (kg) | 1.5 |
Operating conditions | |
Operating temperature | -35°C to +55°C |
Daily average temp | <+40°C |
Altitude | <3500 meters |
Condition | No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current. |
Type |
LZCT723-10 | LZCT723-10 | ||||
---|---|---|---|---|---|---|
Purpose | Measuring current transformer | Protection current transformer | ||||
Ratio | Accuracy class and rated load(VA) | Accuracy class and rated load(VA) | ||||
I1/I2 | 0.2S | 0.2 | 0.5 | 10P15 | 10P10 | 10P5 |
30/1 | 1.5 | 0.5 | ||||
50/1 | 1.5 | 1.25 | ||||
75/1 | 2 | 1 | 2 | |||
100/1 | 2.5 | 1.5 | 2.5 | |||
200/1 | 3 | 1.25 | 2.5 | |||
300/1 | 2.5 | 3.5 | 1.25 | 2.5 | ||
400/1 | 2.5 | 3.5 | 5 | 1.25 | 2.5 | |
500/1 | 3.5 | 5 | 7.5 | 1.25 | 3 | |
600/1 | 5 | 7.5 | 10 | 1.5 | 3 | |
50/5 | 1 | |||||
75/5 | 1.5 | 1.5 | ||||
100/5 | 2.5 | 2.5 | ||||
150/5 | 3.75 | 2.5 | ||||
200/5 | 2.5 | 5 | 2.5 | 3.75 | ||
300/5 | 2.5 | 3.75 | 7.5 | 2.5 | 6.25 | |
400/5 | 5 | 7.5 | 10 | 3.75 | 7.5 | |
500/5 | 5 | 7.5 | 10 | 3.75 | 10 | |
600/5 | 7.5 | 12.5 | 15 | 3.75 | 10 |