MID Vlotage Split Current Transformer

Product Details
Customization: Available
Application: Electronic, Instrument, Position Sensor, Audio, Lighting
Type: Current Transformer
Still deciding? Get samples of US$ 80/Piece
Request Sample
Gold Member Since 2013

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
5000000 RMB
Plant Area
>2000 square meters
  • MID Vlotage Split Current Transformer
  • MID Vlotage Split Current Transformer
  • MID Vlotage Split Current Transformer
  • MID Vlotage Split Current Transformer
  • MID Vlotage Split Current Transformer
  • MID Vlotage Split Current Transformer
Find Similar Products

Basic Info.

Model NO.
Lczk350-10
Phase
Single
Operation Condition
Indoor
Usage
Measurement
Winding Form
Single Layer & Tightly Wound Type
Insulating Medium
Epoxy Resin
Installation
Active Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Model
Current Transformer for Mv
Rated Voltage
35kv
Rated Secondary Current
5A or 1A
Rated Frequency
50Hz or 60Hz
Accuracy
0.5s/0.5/1
Transport Package
Standard Export Box
Specification
LZCK
Trademark
GFUVE
Origin
Beijing, China
HS Code
8504311000
Production Capacity
10000PCS/Month

Product Description

Split core Current transformer for MV
MID Vlotage Split Current Transformer
LZCK series instrument current transformers applicable for AC power system 35kV and measurement of current of power supply equipment below 10KV, and microcomputer protection. This type of current transformer employs imported silicon steel which with high permeability as magnetic material, have the characteristics of Small magnetic circuit loss and can be cut, its semicircular core and secondary windings employ high quality epoxy resin vacuum, casting in plastic-case which is flame retardance anti-moisture, stable performance, no maintenance.
Working conditions:
Ambient temperature: -35° C~+55° C, not exceeding +40° C.
The Height of above sea level: 0~ 3000m.
Atmosphere conditions: No highly polluted, errosion, erosiveness, radioactivity gases.
(continuous working under the rated current is allowed)
(P2 represents for primary polar end, S1, S2 represent for secondary polar end
P2 and S2 are subtractive polarity.
Technical parameters: :
Rated frequency: : 50Hz or 60Hz
Rated secondary current: 5A or 1A
Secondary winding power frequency withstand voltage: 3kV, 1min
Safety Factor Rating (FS) < 5
Standard of Application: GB1208-2006; IEC 60044-1; NTC 2205
Accuracy Class: 0.5S or 0.5, 1;
Item Name
Range of primary rated current
Range of Rated load
(mm)(Description)
(Weight)(kg)

Item Name
 

Range of primary rated current
 

Range of Rated load
 

(mm)(Description)
 

(Weight) ( kg )
 

LZCK110-10
 

300-600A
 

≤5VA
 

φ64×φ104×32
 

0.6
 

LZCK310-10
 

300-600A
 

≤5VA
 

φ50×φ110×32
 

0.6
 

LZCK322-10
 

30-600A
 

≤10VA
 

φ50×φ110×52
 

1.6
 

LZCK350-10
 

30-600A
 

≤25VA
 

φ50×φ110×105
 

3.1
 

LZCK020-10
 

300-600A
 

≤5VA
 

φ55×φ86×50
 

0.5
 

LZCK830-35
 

50-600A
 

≤10VA
 

φ66×φ130×70
 

2.0
 