| Customization: | Available |
|---|---|
| Type: | Electromagnetic |
| Output Signal Type: | Analog Output |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency

| FUD-Type-Input-Power Supply-Output |
|
| Type |
3I: Three Phase AC Current Transducer 3U: Three Phase AC Voltage Transducer |
| AC Input |
A1: 0~1A, A2: 0~5A, A3: 0~10A. V0: 0~70V, V1: 0~120V, V2: 0~250V, V3: 0~300V, V4: 0~450V, V5: 0~500V. |
| Power Supply |
P1: AC110V±10%, P2: AC220V±15%, P3: AC110V~330V. |
| DC Output |
O1: 0~5V, O2: 1~5V, O3: 0~20mA, O4: 4~20mA, O5: RS485. |
| Example 1: FUD-3I-A2-P2-O4 |
|
| FUD Series Three Phase AC Current Transducer |
Input: AC 0~5A |
| Power Supply: AC220V±15% |
|
| Output: DC 4~20mA |
|
| Example 2: FUD-3U-V2-P2-O4 |
|
| Details: FUD Series Three Phase AC Voltage Transducer |
Input: AC 0~250V |
| Power Supply: AC220V±15% |
|
| Output: DC4~20mA |
|
| Please check the Type, Input range, Output range and Power supply at your order. |
|
| Standard |
GB/T 13850-1998, IEC688:1992 |
| Accuracy |
0.2%, 0.5% |
| Consumption |
≤5VA |
| Accutacy drift |
Annual Variation < 0.2% |
| Insulation Voltage |
AC 2kV/min.1mA (Between Input ~ Output / Power) |
| Insulation Resistance |
≥20MΩ (DC500V) |
| Surge voltage |
5KV (Peak Value), 1.2/50μs |
| Response Time |
≤350ms |
| Input Range |
AC 0~10A ,AC 0~500V(Optional), 50/60Hz |
| Absorbed Power |
<0.5VA/450V, <0.2VA/100V, <0.1VA/5A |
| Overload |
Current: 2 times continuous,30 times /1s .Voltage: 2 times continuous |
| Load Resistance |
Current output: RL≤550Ω Voltage output: RL≥2kΩ |
| Working environment |
Temperature: -10~50°C RH: 20~90%, Without condensation |
| Storage conditions |
Temperature: -40~70°C RH: 20~95%, Without condensation |
| Installation |
35mm DIN Sliding-way or M4 screws |
| Dimension |
110mm×75mm×120mm |