100/5A Epoxy Resin Cast Split Core Current Transformer

Product Details
Customization: Available
Application: Electronic, Instrument
Type: Current Transformer
Gold Member Since 2013

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
5000000 RMB
Plant Area
>2000 square meters
  • 100/5A Epoxy Resin Cast Split Core Current Transformer
  • 100/5A Epoxy Resin Cast Split Core Current Transformer
  • 100/5A Epoxy Resin Cast Split Core Current Transformer
  • 100/5A Epoxy Resin Cast Split Core Current Transformer
Find Similar Products

Basic Info.

Model NO.
LZCK350-10
Phase
Single
Operation Condition
Indoor
Usage
Protection, Measurement
Winding Form
Single Layer & Tightly Wound Type
Insulating Medium
Common Insulating Materials
Installation
Active Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Model
100/5A Epoxy Resin Cast Split Core Current Transfo
Keyword
100/5A Split Core Current Transformer
Rated Primary Current
20-600A
Rated Secondary Current
5A or 1A
Rated Frequency
50Hz or 60Hz
Accuracy Class
0.5%, 1%, 3%
Weight (Kg)
3.1
Transport Package
Standard Export Wooden Box
Specification
50mmx110mmx105mm
Trademark
GFUVE
Origin
Beijing, China
Production Capacity
10000pieces/Month

Product Description

100/5A Epoxy Resin Cast Split Core Current Transformer
LZCK series resin split core current transformer is suitable forcurrent measurement and microcomputer protection of electrical equipment in 10KV and 35KV AC power system.It is widely used in compact fully insulated ring network switchgears such as ABB-Safe Ring/Safe plus...and cable distribution boxes.The transformer can be directly installed at the inlet andoutlet cables.The slice is imported silicon material. Thesemicircular ring core and secondary windings arevacuum poured by insulated resin.
100/5A Epoxy Resin Cast Split Core Current Transformer
Parameters
Technical parameters  
Standards IEC60044-1; IEC 61869-2; NTC 2205; GB1208-2006
Rated primary current 20-600A
Rated load ≤25VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Rated short-me thermal current 40kA, 1S
Rated connuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS ≤10
Mechanical parameters  
Dimensions (W×D×H) (mm) φ50xφ110x105
Weight (kg) 3.1
Operang condions  
Operang temperature -35°C to +55°C
Daily average temp < +40°C
Altude <3500 meters
Condion No existence of severely begrimed, erosive and radioacve gas in the air. Permission of long-term operaon under rated current.
Technical data
Type LZCK350-10 LZCK350-10 LZCK350-10
Purpose Measuring current transformer Protecon current transformer Double winding current transformer
Rao Accuracy class and rated burden(VA) Accuracy class and rated load (VA) Composite accuracy class and rated load (VA)
I1/I2 0.5 1 3 10P15 10P10 10P5 0.5 1 10P10 10P5
20/1     0.5     0.75        
30/1   0.5 1.5   0.75 1.25        
50/1   1 2   1.25 2        
75/1 2 2.5 3.75 1.25 2 3   2 1 2
100/1 2.5 3.75 5 2 2.5 5 2 2.5 1.5 2.5
200/1 5     3 5 7.5 2.5   2  
300/1 10     3 5 7.5 3.75   2.5  
400/1 10     3 5 10 5   2.5  
500/1 25     3.75 6.25 10 5   2.5  
600/1 25     5 7.5 10 7.5   5  
Type LZCK350-10 LZCK350-10 LZCK350-10
Purpose Measuring current transformer Protecon current transformer Double winding current transformer
Rao Accuracy class and rated burden(VA) Accuracy class and rated load (VA) Composite accuracy class and rated load (VA)
600/1 25     5 7.5 10 7.5   5  
50/5     2.5     2        
75/5     2.5     3        
100/5 2.5   3.75     5   2.5   2.5
200/5 7.5           2.5 5   2.5
300/5 10           5   2 2.5
400/5 15           7.5   2.5 5
500/5 25           7.5   2.5 5
600/5 30           10   3 7.5

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier
Product Groups
More