Customization: | Available |
---|---|
Application: | Instrument |
Type: | Current Transformer |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical parameters | |
Standards | IEC60044; IEC 61869; ANSI/IEEE C57.13 |
Rated primary current | 5-6000A |
Rated load | ≤40VA |
Rated frequency | 50Hz or 60Hz |
Rated secondary current | 5A or 1A |
Rated short-time thermal current | 180kA, 1S |
Rated dynamic current | 260kA |
Rated insulation level | 12/42/75KV |
FS | ≤10 |
Mechanical parameters | |
Material | Epoxy resin |
Weight (kg) | 23 |
Operating conditions | |
Operating temperature | -25°C to +55°C |
Daily average temp | <+40°C |
Storage temperature | -40°C to +70°C |
Altitude | <1000 meters |
Condition | No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current. |
Raed Primary | Class Combinaon |
Accuracy class and Rated output (VA) |
Short-me thermal current | Rated dynamic current | ||
Current(A) | 0.2 | 0.5 | 10P | (kA/S) | (kA) | |
5-300 | 0.2/0.5 0.2/10P20 0.5/10P20 |
20 | 40 | 40 | 150I1n | 375I1n |
400-500 | 45 | 112.5 | ||||
600-800 | 0.2/0.5 0.2/10P25 0.5/10P25 |
80 | 160 | |||
1000 | ||||||
1200-1250 | 0.2/0.5 0.2/10P30 0.5/10P30 |
40 | 100 | 180 | ||
1500-6000 | 180 | 260 |