Customization: | Available |
---|---|
After-sales Service: | 24 Hour Service |
Warranty: | 3 Years |
Still deciding? Get samples of US$ 12000/Set
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Metrological service center;
Laboratories of power utilities;
Electricity meter manufacturers;
Electricity power bureau & power company;
National Metrology and testing department;
Electrical Department of industrial and mining enterprises;
AMI design center;
Electrical laboratory;
Energy meter R & D;
Watt-hour meter factory;
Phase angle precision less than 0.02°;
Multi range, automatic range switching;
High stability 0.005%/min, high reliability;
Vector diagram function;
Waveform display function;
7 inch TFT color LCD display;
Energy register testing function;
Measuring 2nd~51st harmonics;
High accuracy class up to 0.04%;
0-576V, 1mA-120A, 40-70.000Hz;
Metal structure, strong and reliable;
Suit for testing in the lab and on site;
Current measurement with direct and clamp on ct;
Programmable pulse constant output up to 750000;
5A, 10A, 20A, 100A, 200A, 300A, 500A, 1000A, 3000A, 5000A optional
Electrical parameters | |
---|---|
Accuracy class | 0.04%, 0.05%, 0.1% |
Power supply | 45-450V AC, 50/60Hz |
Power consumption | 10VA |
Voltage measurement | |
Range | 0-576.000V |
Error | ±0.02% (40V-560V) ±0.05% (5V-40V) |
Harmonic | 2nd- 51st |
Current measurement(direct)t | |
Range (direct connection) | 1mA-30.000A |
Error (direct connection) | ±0.02% (25mA-30A) ±0.04% (1mA-25mA) |
Harmonic | 2nd- 51st |
Clamp on ct (indirect) | |
Range (Standard) | 1mA-120.000A |
Error (Standard) | ±0.04% (100mA-120A) ±0.1% (1mA-100mA) |
Harmonic | 2nd- 51st |
Clamp on ct optional | 5A, 10A, 20A, 100A, 200A, 300A, 500A, 1000A, 3000A, 5000A |
Power measurement error | |
Active power | ±0.04% (0.01A-30A) ±0.1% (0.001A-0.01A) |
Reactive power | ±0.1% (0.001A-30A) |
Energy measurement error | |
Active energy | ±0.04% (0.01A-30A) ±0.1% (0.001A-0.01A) |
Reactive energy | ±0.1% (0.001A-30A) |
Phase angle | |
Range | 0°-360.000° |
Resolution | 0.005° |
Error | ±0.02° |
Power factor | |
Range | -1.00000-0-1.00000 |
Resolution | 0.0005 |
Error | 0.0001 |
Frequency | |
Range | 40.0000-70.0000Hz |
Resolution | 0.0005 |
Error | ±0.001 |
Pulse output | |
Output channel | 1 |
Energy constant | 1-9999999 |
Pulse ratio | 1:1 |
Output level | 5V |
Output rated frequency | 60KHz, max 86.4KHz |
Pulse input | |
Input channel | 1 |
Input level | 5-24V or 3-12V |
Input frequency | Max. 2MHz |
Function | |
LCD Display | 7 inch 800x480 pixel touch TFT |
Vector diagram | Yes |
Waveform | Yes |
Key | 18PCS |
Energy accumulation | Yes |
Self-calibration | Yes |
Data storage | Yes |
PC software | Optional |
Communication port | RS232 & USB |
Standard | |
Standard | IEC 62053-21,22, 23; IEC 60736; ANSI C12.20-2002; JJG 597-2005; JJG596-2012; JJG 1085-2013; JJF 68-2019; DL/T 826-2002; DL/T 1478-2015; DL/T 448-2016; GB/T 33708-2017 |
Safety | |
Isolation protection | IEC 61010-1:2001 |
Measurement Category | 300 V CAT III, 600 V CAT II |
Degree of protection | IP65 |
Declaration of conformity | CE & CNAS certified |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 365 x 269 x 151 |
Weight (kg) | 3 |
Environmental conditions | |
Ambient temperature | 0°C to 40°C |
Storage temperature | -20°C to +65°C |
Relative humidity | 10%-85% |
Temperature coefficient | ≤0.0005% /ºC |
Influence of external fields | ≤0.05 %/mT |