Gfuve Portable CT Current Transformer Analyzer with 50kv Excitation Knee Point
Contact Supplier
Product Highlights
- Comprehensive Testing Functions: Supports CT, PT, and TYP class testing including magnetization curves, polarity, and degauss.
- Portable Design with Touch Screen: Weighs only 4.5kg with a 7-inch TFT color touch LCD and built-in mini printer for field use.
- Wide Excitation Capability: Features 50kV excitation knee point calculation and output voltage up to 100Vrms.
- Flexible Power Supply Options: Operates on AC 220V/120V or battery, supporting 50/60Hz frequency variation from 0.1-60Hz.
- Data Storage and Transfer: Supports USB flash disk for data dumping and automatic calculation of excitation knee points.
- International Standard Compliance: Meets IEC60044-1/6, IEC61869-2, ANSI/IEEE C57, and GB1207/1208 standards.
Product Attributes
- Customization
- Available
- Type
- Current Transformer Tester
- Accuracy Grade
- 0.02%
- Model NO.
- GF1061
- Loading Method
- Static Load
- Display
- Digital
- Control
- Computer Control
- Weight
- 4.5kg
- Power Source
- AC220V
- Names
- Current Transformer Analyzer
- Applications
- CT, PT Error Test
- CT Ratio
- 1-50000
- PT Ratio
- 1-10000
- LCD
- 7 Inch TFT Color Touch LCD
- Color
- Yellow
- Resistance
- 0.1-1000Ω
- Reference Standards
- IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57.
- Transport Package
- Standard Export Carton Packaging
- Specification
- GF1061 0.02%
- Trademark
- GFUVE
- Origin
- Beijing, China
- HS Code
- 8470501000
- Production Capacity
- 500sets/Month
Product Images of Gfuve Portable CT Current Transformer Analyzer with 50kv Excitation Knee Point
Find Similar Products
Product Description
GF1061 portable Current transformer analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.
Main functions
| I. Current Transformer (CT) | II. Voltage Transformer (PT) |
|---|---|
| 1. Magnetization curve | 1. Excitation characteristic test |
| 2. Transformation ratio test | 2. Transformation ratio test |
| 3. Polarity | 3. Polarity |
| 4. 5% and 10% error curve | 4. Ratio error, phase error |
| 5. Accuracy limiting factor (ALF) | 5. Degauss |
| 6. Degauss | 6. Calculation of knee point value |
| 7. Ratio error, phase error | 7. Actual secondary load test (burden test) |
| 8. Automatic calculation of excitation knee point value |
8. Resistance test |
| 9. Actual secondary load test (burden test) | |
| 10. Resistance test | |
| 11. Secondary time constant (Ts) | |
| 12. Remanence coefficient (Kr) | |
| 13. Transient dimensioning factor (Ktd) | |
| 14. Peak instantaneous error (Er) | |
| 15. Magnetizing inductance (LU) | |
| 16. Instruments security factor(FS) | |
| 17. Composite error | |
Parameters
| Electrical parameters | ||
|---|---|---|
| Accuracy | 0.05% | |
| Power supply | AC 220V±10% or AC 120V±10%, 50/60Hz or Battery | |
| Output voltage | 0-100Vrms | |
| Output current | 0-5Arms (20A peak-value) | |
| Output power | 0-400 VA (1500 VApeak) | |
| Automatic frequency variation range | 0.1-60Hz | |
| Equivalent excitation voltage | ≤5000V | |
| Accuracy | ≤0.5% | |
| Secondary winding DC resistance measurement | Range | 0.1-1000Ω |
| Accuracy | ≤0.05% | |
| Secondary actual load measurement | Range | 5VA-1000VA |
| Accuracy | ≤0.5%±0.1VA | |
| CT/PT phase error measurement | Accuracy | ±1min (typical) / 3 min (guaranteed) |
| Resolution | 0.1min | |
| CT ratio error measurement | Range | 1-50000 |
| Accuracy | ≤0.05% | |
| PT ratio error measurement | Range | 1-10000 |
| Accuracy | ≤0.05% | |
| Standards | ||
| Reference standards | GB1207-2006, GB1208-2006, GB16847-1997 IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57.13 |
|
| Safety standards | GB 4793.1-2007 | |
| EMC | EMC standard 89/336/EEC | |
| FCC Subpart B of Part 15 Class A | ||
| IEC 1000-4-2 /3 /4 /6 | ||
| Mechanical parameters | ||
| Overall dimension (L x W x H) (mm) | 280 x 250 x 160 | |
| Weight (kg) | ≤4 | |
| Environmental conditions | ||
| Relative humidity | Relative humidity 5%-95% not condensing | |
| Operating temperature | -10°C to +50°C | |
| Storage temperature | -20°C to +70°C | |
| Altitude | ≤1000m | |
PHOTO
About the Supplier
Company Profile
Beijing GFUVE Electronics Co., Ltd. Was established in 2005. It combined science, industry and trade together as one high-tech enterprise. GFUVE mainly produces split core current transformer, high voltage ammeter recorder, IEC61850 test suite software, meter test equipment, current probe, reference standard meter, phantom load power source, electrical measurement instrument, relay test set, transformer test, CT analyzer, Test equipment, and power meter, power analyzer, intelligent digital meter, transducer, handheld terminal and split core current transformer, voltage transformer and current transformer models etc.
GFUVE is a leader manufacturer of energy meter test products and high voltage ammeter recorder in China. It is professional in energy meter test system, energy meter portable tester and related accessory of current probe. The product of high voltage ammeter recorder develops very quickly in the market. Our company has achieved certification to ISO9001. The products are sold to over 30 provinces in China and exported to overseas including South America, Middle East, South east and Africa.
We have been contributing ourselves to developing the durable and stable products for the usage of the power system. Contact us now for further business relationship. We are here to provide you the best service.
About Our Factory & Business Background
- Address
- Bldg. 2-1111, Joy Mansion, No. 99 Chaoyang North Road, Chaoyang District, Beijing, China
- Terms of Payment
- LC, T/T, PayPal, Western Union
- International Commercial Terms(Incoterms)
- FOB, CIF, FCA, EXW
- Average Lead Time
-
Peak Season Lead Time: one month
Off Season Lead Time: within 15 workdays - Nearest Port
- TIANJING
Our Production Capability & Technical Expertise
Our Industry Experience & Global Business Record
- Export Year
- 2010-08-01
- Main Markets
- North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe
FAQ
- What is the accuracy grade of the analyzer?
- The analyzer offers an accuracy grade of 0.02% for CT and PT ratio error measurement.
- Can this device be used for field testing?
- Yes, it is portable at 4.5kg, features a built-in printer, and supports USB data storage for field use.
- What types of transformers can be tested?
- It supports measurements for Protection (P) class CT, Metering (M) class CT, PT, and TYP class CT.
- Does the device support automatic knee point calculation?
- Yes, it includes automatic calculation of excitation knee point values and magnetization curves.
- What standards does the analyzer comply with?
- It complies with IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57, and various GB standards.
- What is the maximum output power?
- The device provides an output power of 0-400 VA with a peak value of 1500 VA.
Send your message to this supplier
People who viewed this also viewed
-
US$3,850.00 / Set
-
US$8,585.00 / Set
-
US$15,858.00 / Piece
-
US$12,828.00 / Piece
Find Similar Products By Category
- Supplier Homepage
- Products
- Transformer Test Equipment
- CT analyzer
- Gfuve Portable CT Current Transformer Analyzer with 50kv Excitation Knee Point
Related Categories
Hot Searches
- Current Meter Factories
- Analyzer Equipment Factories
- Spectrum Analyzer Factories
- Portable Detector
- Analyzer Portable
- Current Analyzer
- Portable Gas Analyzer
- Portable Power Analyzer
- Portable Laboratory Analyzer
- Current Transformer Analyzer Bulkbuy