Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 10000/Set
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
TEST-901 Electric 1000A Heavy Current Primary Current Injection Test Equipment for Break Circuit
TEST-901 1000A primary current injection test equipment adopts ARM Chip to control its output process and large capacity of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value, second current value, turn ratio and the action time. Packing is used as aluminum alloy body with PC panel. TEST-901 is mainly applied to CT turn ratio testing in the power system and contact resistance test which need large current.
This powerful test system is designed for primary injection testing of protective relay equipment and circuit breakers. It is also used to test the turns ratio of current transformers and for other applications that require high variable currents.
Electrical parameters | |
---|---|
Accuracy | ±0.5% |
Power Supply(AC) | 220V±10%·25A, 50Hz/60Hz or 110V±10%·50A, 50Hz/60Hz |
Current Output (AC) | 1000A·5V or 500A·10V |
Capacity | 5KVA |
The current output waveform distortion | ≤5% |
Dual protection | overload electronic protection and software protection |
Primary current | |
Range | 0-1100A |
Resolution | 0.1A |
Accuracy | <0.5% |
Secondary measurement | |
Range | 0-6A |
Resolution | 0.001A |
Accuracy | <0.5% |
Current duration | |
1000A range | 1000A 2-3minutes 500A 3-6minutes |
500A range | 500A 2-3minutes |
With timer | |
Range | 0.0001~999.99S |
Resolution | 0.001S |
Accuracy | <0.5%±5 words |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 430×260×260 |
Weight(kg) | 25 |
Environmental conditions | |
Temperature | -10°C to 40°C |
Relative humidity | ≤80% |
Model | ACCU RACY |
Primary current |
AMMETER (0-6A) |
TIMER | POWER | INJECTION CURRENT TIME | DIMENSION(W×D×H)(mm) | WEIGHT | REMARK |
---|---|---|---|---|---|---|---|---|---|
TEST-901 | 0.5% | 0-1100A | YES | YES | 5KVA | 1000A: 2-3min; 500A:3-6min |
430×260×260 | 25KG | Integrated structure |
TEST-902 | 0.5% | 0-2200A | YES | OPTIONAL | 12KVA | 2000A:2-3min; 1000A:3-6min |
360×300×295 and 320×300×300 | 35KG+15KG | Fission structure |
TEST-903 | 0.5% | 0-3300A | YES | OPTIONAL | 15KVA | 3000A:2-3min; 1500A:3-6min |
380×350×360 and 340×290×420 | 48KG+42KG | Fission structure |
TEST-905 | 0.5% | 0-5500A | YES | OPTIONAL | 25KVA | 5000A:2-3min; 2500A:3-6min |
430×430×445 and 550×450×600 | 68KG+55KG | Fission structure |