800/5A Split Core Zero Sequence Current Transformers

  • Audited Supplier
  • 14 yrs

Contact Supplier

Still deciding? Get samples of $ !
Request Sample

Product Highlights

  • Split Core Design: Allows direct installation on existing cables without disconnecting power lines.
  • High Accuracy Options: Available in 0.5, 1, 3, 10P15, 10P10, and 10P5 accuracy classes for measuring and protection.
  • Wide Current Range: Rated primary current from 500A to 1500A with secondary options of 5A or 1A.
  • Robust Construction: Vacuum poured epoxy resin insulation with imported silicon material for durability.
  • Multi-Standard Compliance: Meets IEC60044-1, IEC61869-2, NTC 2205, ANSI C57.13, and GB1208-2006 standards.
  • Customization Available: Special specifications, ratios, and parameters can be customized according to customer needs.
  • Compact Dimensions: Dimensions of 120x185x100mm and weight of 7kg for easy integration in switchgears.

Product Images of 800/5A Split Core Zero Sequence Current Transformers

800/5A Split Core Zero Sequence Current Transformers pictures & photos
800/5A Split Core Zero Sequence Current Transformers
800/5A Split Core Zero Sequence Current Transformers pictures & photos
800/5A Split Core Zero Sequence Current Transformers
800/5A Split Core Zero Sequence Current Transformers pictures & photos
800/5A Split Core Zero Sequence Current Transformers
800/5A Split Core Zero Sequence Current Transformers pictures & photos
800/5A Split Core Zero Sequence Current Transformers
800/5A Split Core Zero Sequence Current Transformers pictures & photos
800/5A Split Core Zero Sequence Current Transformers
800/5A Split Core Zero Sequence Current Transformers pictures & photos
800/5A Split Core Zero Sequence Current Transformers
  • 800/5A Split Core Zero Sequence Current Transformers
    800/5A Split Core Zero Sequence Current Transformers
  • 800/5A Split Core Zero Sequence Current Transformers
    800/5A Split Core Zero Sequence Current Transformers
  • 800/5A Split Core Zero Sequence Current Transformers
    800/5A Split Core Zero Sequence Current Transformers
  • 800/5A Split Core Zero Sequence Current Transformers
    800/5A Split Core Zero Sequence Current Transformers
  • 800/5A Split Core Zero Sequence Current Transformers
    800/5A Split Core Zero Sequence Current Transformers
  • 800/5A Split Core Zero Sequence Current Transformers
    800/5A Split Core Zero Sequence Current Transformers

Find Similar Products

Product Description

LZCK2500-10 800/5A 35KV SPLIT CORE ZERO SEQUENCE CT CURRENT TRANSFORMERS

LZCK series split core zero sequence ct current transformers is suitable for current measurement and microcomputer protection of electrical equipment in 10KV and 35KV AC power system. It is widely used in compact fully insulated ring network switchgears such as ABB-Safe Ring/Safe Plus...and cable distribution boxes. The current transformer can be directly installed at the inlet andoutlet cables.The slice is imported silicon material. Thesemicircular ring core and secondary windings arevacuum poured by insulated resin.
OUTLINE DRAWING
800/5A Split Core Zero Sequence Current Transformers
WIRING DIAGRAMS
P1, P2 is primary polarity terminal, S1, S2 is secondary polarity terminal.
P2, S2 is homonymous terminals (subtractive polarity).
PARAMETERSTechnical parameters Mechanical parameters Operating conditions
Standards IEC60044-1; IEC 61869-2; NTC 2205; ANSI C57.13; GB1208-2006
Rated primary current 500-1500A
Rated load ≤20VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS≤10
Dimensions (W×D×H) (mm) φ120xφ185x100
Weight (kg) 7
Operating temperature -35°C to +55°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Altitude <3500 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.
SELECTION GUIDETypeLZCK2500-10LZCK2500-10PurposeMeasuring current transformerProtection current transformerRatioAccuracy class and rated load(VA)Accuracy class and rated load(VA)
I1/I2 0.5 1 3 10P15 10P10 10P5
300/5 5 5 5 2.5 5 7.5
400/5 5 5 5 2.5 5 7.5
500/5 5 7.5 7.5 5 7.5 10
600/5 5 7.5 7.5 5 7.5 10
800/5 10 10 10 5 10 15
1000/5 10 15 15 5 10 15
1200/5 15 20 20 10 15 20
1500/5 15 20 20 10 15 20
SELECTION GUIDE ModelPrimary rated currentRated loadAperture (mm)Description (mm)Weight (kg)MaterialWater-proof
LZCK-55 100-1500A ≤10VA φ55 180×138×52 2 ABS+Resin  IP65
LMCK185-10 300-3000A ≤25VA φ185 350×283×55 4.5 ABS+Resin  IP65
LZCK310-10 300-600A ≤10VA φ50 φ50 x φ110 x 32 1 Resin silicon case (option)
LZCK322-10 30-600A ≤10VA φ50 φ50 x φ110 x 52 1.6 Resin silicon case (option)
LZCK350-10 20-600A ≤25VA φ50 φ50 x φ110 x 105 3.1 Resin silicon case (option)
LZCK720-10 20-1000A ≤25VA φ60 φ80 x φ110 x 50 2.1 Resin silicon case (option)
LZCK2500-10 500-1500A ≤20VA φ120 φ120 x φ185 x 100 7 Resin silicon case (option)
LZCG530-10 30-600A ≤20VA φ45 φ45 x φ120 x 65 2.1 Resin silicon case (option)
LZCG930-10 100-1500A ≤25VA φ60 φ60 x φ155 x 60 3.6 Resin silicon case (option)
LZCT722-10 20-600A ≤10VA φ82 φ82 x φ130 x 55 2.3 Resin silicon case (option)
ORDERING INFORMATION
Be sure to the type, current ratio, accuracy class, rated load and use of the products when you plan to make a order. Special specifications could be customized.All kinds of different specifications and parameters current transformers can be made according to your needs.

About the Supplier

Watch Video
Watch Video
Beijing GFUVE Electronics Co., Ltd.
Beijing GFUVE Electronics Co., Ltd.
Beijing GFUVE Electronics Co., Ltd.
Beijing GFUVE Electronics Co., Ltd.
Beijing GFUVE Electronics Co., Ltd.
Beijing GFUVE Electronics Co., Ltd.
Beijing GFUVE Electronics Co., Ltd.
Beijing GFUVE Electronics Co., Ltd.

About Our Factory & Business Background

Address
Bldg. 2-1111, Joy Mansion, No. 99 Chaoyang North Road, Chaoyang District, Beijing, China
Terms of Payment
LC, T/T, PayPal, Western Union
International Commercial Terms(Incoterms)
FOB, CIF, FCA, EXW
Average Lead Time
Peak Season Lead Time: one month
Off Season Lead Time: within 15 workdays
Nearest Port
TIANJING

Our Production Capability & Technical Expertise

Main Products
Current Transformer, Energy Meter Calibration, Power Quality Analyzer, Test Equipment, CT PT Analyzer, Relay Test Equipment, Split Core Current Transformer, Current Probe, Voltage Transformer, Power Meter

Our Industry Experience & Global Business Record

Export Year
2010-08-01
Main Markets
North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe

FAQ

What is the rated primary current range?
The rated primary current ranges from 500A to 1500A.
Can the current transformer be customized?
Yes, special specifications, ratios, and parameters can be customized according to your needs.
What standards does this product comply with?
It complies with IEC60044-1, IEC61869-2, NTC 2205, ANSI C57.13, and GB1208-2006.
What is the accuracy class for protection?
Protection accuracy classes available include 10P15, 10P10, and 10P5.
What is the lead time for orders?
Peak season lead time is one month, while off-season lead time is within 15 workdays.
What payment terms are accepted?
Accepted payment terms include LC, T/T, PayPal, and Western Union.

Send your message to this supplier

Contact Information
Recipient
Message

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

Product Groups

Product Catalogs