TEST-902 Primary Current Injection Testing equipment
TEST-902 2000A primary current injection tester adopts ARM chip to control the output process and large capacity of toroidal transformer. It is equipped with LCD screen display current meter, also showed primary current value, secondary current value, turn ratio and the action time. Aluminum alloy body with PC panel component the shell. TEST-902 primary current injection tester is mainly applied to test CT turn ratio and polarity in the power system, the contact resistance, protection relay, low voltage & high voltage circuit breaker protection test and high voltage generator test etc, which need large current on-site or in the lab.
Electrical parameters | |
---|---|
Accuracy | ±0.5% |
Power Supply (AC) | 220V±10%·50A, 50Hz/60Hz or 110V±10%·100A, 50Hz/60Hz |
Current Output (AC) | 2000A·6V or 1000A·12V |
Capacity | 12KVA |
The current output waveform distortion | ≤5% |
Primary current | |
Range | 0-2200A |
Resolution | 0.1A |
Accuracy | <0.5% |
Secondary measurement | |
Range | 0-6A |
Resolution | 0.001A |
Accuracy | <0.5% |
Current duration | |
2000A range | 2000A 2-3minutes 1000A 3-6minutes |
1000A range | 1000A 2-3minutes |
Continuous output | 800A |
With timer | |
Range | 0.0001~999.999S |
Resolution | 0.001S |
Accuracy | <0.2% ±5 words |
Standard | |
Standard | IEC61010-1;IEC 61326-1 |
Communication port | RS232 |
Cable | length 4x6m, 95mm² |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 360×300×295 and 320×300×300 |
Weight(kg) | Control Host 35kg, External voltage regulator weight 15kg |
Structure | Integrated or split optional |
Environmental conditions | |
Operating Temperature | -10°C to 50°C |
Storage Temperature | -40°C to 70°C |
Relative humidity | ≤95%,on-condensing |
Model | Accuracy | Primary Current | Ammeter(0-6A) | Timer | Power | Injection Current time | Dimension(W×D×H) (mm) | Weight | Remark |
---|---|---|---|---|---|---|---|---|---|
TEST-901 | 0.5% | 0-1100A | YES | YES | 5KVA | 1000A: 2-3min; 500A:3-6min |
430×260×260 | 25KG | Integrated structure |
TEST-902 | 0.5% | 0-2200A | YES | YES | 12KVA | 2000A:2-3min; 1000A:3-6min |
360×300×295 and 320×300×300 | 35KG+15KG | Fission structure |
TEST-903 | 0.5% | 0-3300A | YES | YES | 15KVA | 3000A: 2-3min; 1500A:3-6min |
380×350×360 and 340×290×420 | 48KG+42KG | Fission structure |
TEST-905 | 0.5% | 0-5500A | YES | YES | 30KVA | 5000A:2-3min; 2500A:3-6min |
430×430×445 and 550×450×600 | 68KG+55KG | Fission structure |