Customization: | Available |
---|---|
Accuracy: | 0.02%, 0.05%, 0.1% |
Power Supply: | One Phase AC 100-265V, Frequency 50/60Hz. |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Accuracy class | 0.02%, 0.05%, 0.1% |
Power Supply | One Phase AC 100-265V, frequency 50/60Hz. |
AC Voltage Output | |
---|---|
Range | 57.7V, 100V, 220V, 380V; max 600V |
Adjustment range | (0-120)%RG(1) |
Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability | 0.01%/120s |
Distortion | 0.1% (Non-capacitive load) |
Output load | 25VA or 50VA |
Measuring accuracy | 0.02%RG or 0.05%RG |
AC Current Output | |
Range | 200mA, 1A, 5A, 20A, 100A; max 120A |
Adjustment range | (0-120)%RG |
Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability | <0.01%/120s |
Distortion | ≤0.1% (Non-capacitive load) |
Output load | 50VA or 100VA |
Accuracy | 0.02%RG or 0.05%RG |
Power Output | |
Active power output stability | <0.01%RG/120s |
Reactive power output stability | <0.02%RG/120s |
Active power measuring accuracy | 0.02%RG or 0.05%RG |
Reactive power measuring accuracy | 0.05%RG or 0.1%RG |
Phase Output | |
Output adjustment range | 0°-359.999° |
Output adjustment fineness | 10, 1, 0.1, 0.01 as optional. |
Resolution | 0.01° |
Accuracy | 0.02° |
Power Factor | |
Adjustment range | -1 ~ 0 ~ 1 |
Resolution | 0.0001 |
Measurement accuracy | 0.0005 |
Frequency Output | |
Adjustment range | 40Hz-70Hz |
Output adjustment fineness | 5Hz, 1Hz, 0.1Hz, 0.01Hz as optional. |
Resolution | 0.001Hz |
Accuracy | 0.002Hz |
Voltage /Current/Harmonic Setting | |
Harmonic number | 2-63times |
Harmonic content | 0-40% |
Harmonic phase | 0-359.99 |
Harmonic setting accuracy | (10%±0.1%)RD(2) |
Power Energy Measurement Error | |
Active power energy | 0.02%RG or 0.05%RG |
Reactive power energy | 0.05%RG or 0.1%RG |
Power Pulse Output | |
Power pulse type | active pulse, reactive pulse |
Active power pulse output | 5V, 10mA |
Power Pulse Input | |
Energy pulse type | support active and reactive pulse, the highest frequency power pulse input is 200K. |
Standard | |
Standard | IEC 62053-21,22, 23; IEC 60736; ANSI C12.20-2002; JJG 597-2005; JJG596-2012; JJG 1085-2013; JJF 68-2019; DL/T 826-2002; DL/T 1478-2015; DL/T 448-2016 |
Safety | |
Isolation protection | IEC 61010-1:2001 |
Measurement Category | 300 V CAT III, 600 V CAT II |
Degree of protection | IP20 |
Declaration of conformity | CE & CNAS certified |
Functions | |
LCD | 7 inch touch TFT color LCD |
Communication port | RS232 or USB |
Programmable | Yes |
Meter position | 1pc or 3pcs |
PC control software | Optional |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 455x440x150 |
Weight (kg) | 12 |
Environmental conditions | |
Ambient temperature | -10°C to +40°C |
Relative humidity | 35%-85% |
(1) RG means range, the same as below; (2) RD means the setted harmonic content, harmonic can be a single output, also multiple output. |