Current Transformer Tester Automatic Class 0.02 China High Quality Current Transformer CT Analyzer
Contact Supplier
Product Highlights
- High Precision Accuracy: Offers 0.02% accuracy for DC method testing, ensuring reliable results for metering and protection CTs.
- Comprehensive Testing: Tests CT, PT, and TYP class including ratio, polarity, excitation, saturation, and burden impedance.
- User-Friendly Interface: Features a 7-inch touch TFT LCD and automatic calculation of values based on IEEE and IEC standards.
- Data Management: Supports USB flash disk for data dumping and includes a mini type printer for immediate field printing.
- Wide Application Range: Suitable for manufacturers, labs, and field testing of current transformers, high voltage transformers, and switchgear.
- Robust Performance: Handles large current output up to 1000A and excitation voltage up to 2500Vrms for thorough analysis.
- Standard Compliance: Meets international standards including IEC60044-1, IEC61869-2-2012, and GB1208-2006 for safety and EMC.
Product Attributes
- Customization
- Available
- Certification
- ISO9001, CCC
- Accuracy
- 0.05% 0.1%
- Model NO.
- GF106
- Excitation Output Voltage
- 0-220vrms
- Excitation Output Current
- 0-5arms(20A Peak-Value)
- Weight(Kg)
- 10
- Transport Package
- Standard Export Wooden Box
- Specification
- GF106, 0.05%, 1000A/2500V
- Trademark
- GFUVE
- Origin
- Beijing China
- Production Capacity
- 200set/Month
Product Images of Current Transformer Tester Automatic Class 0.02 China High Quality Current Transformer CT Analyzer
Find Similar Products
Product Description
GF106 PORTABLE 0.02% high accuracy DC method current transformer testing ct analyzer




GF106 portable CT analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.
The CT Analyzer automatically determines all relevant current transformer values and compares the results with the selected standard. The device evaluates the current transformer as per the IEC or IEEE standard within seconds with the push of a button.
It facilitates fast and economical on-site testing and calibration of metering and protection current transformers. Manufacturers of current transformers, high voltage transformers and switchgear also use the CT Analyzer for tests during development and production.
Applications
The following values can be determined using the CT Analyzer:
Accuracy of the ratio and phase angle, taking into consideration the nominal burden and connected burden
CT excitation and saturation
Burden impedance
Winding resistance
Saturated and non-saturated inductance
CT polarity
MAIN FUNCTIONS
| I. Current Transformer (CT) | II. Voltage Transformer (PT) |
| 1. Magnetization curve | 1. Excitation characteristic test |
| 2. Transformation ratio test | 2. Transformation ratio test |
| 3. Polarity | 3. Polarity |
| 4. 5% and 10% error curve | 4. Ratio error, phase error |
| 5. Accuracy limiting factor (ALF) | 5. Degauss |
| 6. Degauss | 6. Calculation of knee point value |
| 7. Ratio error, phase error | 7. Actual secondary load test (burden test) |
| 8. Automatic calculation of excitation knee point value | 8. Resistance test |
| 9. Actual secondary load test (burden test) | |
| 10. Resistance test | |
| 11. Secondary time constant (Ts) | |
| 12. Remanence coefficient (Kr) | |
| 13. Transient dimensioning factor (Ktd) | |
| 14. Peak instantaneous error (Er) | |
| 15. Magnetizing inductance (LU) | |
| 16. Instruments security factor(FS) | |
| 17. Composite error |
PARAMETERS
| Electrical parameters | ||
| Accuracy | 0.2%, 0.5% | |
| Power supply | AC 220V±10% or AC 110V±10%, 50/60Hz | |
| Excitation voltage output | 0-2500Vrms, | |
| Excitation current output | 0-5Arms (20A peak-value) | |
| Large current output | 0-1000A | |
| Electrical parameters - continued | ||
| Accuracy | ≤0.5% (0.2%RD+0.3%RG) | |
| Secondary winding DC resistance measurement | Range | 0.1-300Ω |
| Accuracy | ≤0.5% (0.2%RD+0.3%RG) | |
| Secondary actual load measurement | Range | 5VA-1000VA |
| Accuracy | ≤0.5% (0.2%RD+0.3%RG)±0.1VA | |
| CT/PT phase error measurement | Accuracy | ±4min |
| Resolution | 0.01min | |
| CT ratio error measurement | Range | 5-25000A/5A(5000A/1A) |
| Accuracy | ≤0.5% | |
| PT ratio error measurement | Range | 1-500KV |
| Accuracy | ≤0.5% | |
| Standards | ||
| Reference standards | GB1207-2006, GB1208-2006, GB16847-1997 IEC60044-1, IEC60044-6, IEC61869-2-2012 |
|
| Safety standards | GB 4793.1-2007 | |
| EMC | EMC standard 89/336/EEC | |
| FCC Subpart B of Part 15 Class A | ||
| IEC 1000-4-2 /3 /4 /6 | ||
| Mechanical parameters | ||
| Overall dimension (L x W x H) (mm) | 400 x 240 x 260 | |
| Weight (kg) | ≤23 | |
| Environmental conditions | ||
| Relative humidity | 90RH% | |
| Operating temperature | -10°C to +40°C | |
| Altitude | ≤1000m | |
| Electrical parameters | ||
| Accuracy | 0.2%, 0.5% | |
| Power supply | AC 220V±10% or AC 110V±10%, 50/60Hz | |
| Excitation voltage output | 0-2500Vrms, | |
| Excitation current output | 0-5Arms (20A peak-value) | |
| Large current output | 0-1000A | |
| Electrical parameters - continued | ||
| Accuracy | ≤0.5% (0.2%RD+0.3%RG) | |
| Secondary winding DC resistance measurement | Range | 0.1-300Ω |
| Accuracy | ≤0.5% (0.2%RD+0.3%RG) | |
| Secondary actual load measurement | Range | 5VA-1000VA |
| Accuracy | ≤0.5% (0.2%RD+0.3%RG)±0.1VA | |
| CT/PT phase error measurement | Accuracy | ±4min |
| Resolution | 0.01min | |
| CT ratio error measurement | Range | 5-25000A/5A(5000A/1A) |
| Accuracy | ≤0.5% | |
| PT ratio error measurement | Range | 1-500KV |
| Accuracy | ≤0.5% | |
| Standards | ||
| Reference standards | GB1207-2006, GB1208-2006, GB16847-1997 IEC60044-1, IEC60044-6, IEC61869-2-2012 |
|
| Safety standards | GB 4793.1-2007 | |
| EMC | EMC standard 89/336/EEC | |
| FCC Subpart B of Part 15 Class A | ||
| IEC 1000-4-2 /3 /4 /6 | ||
| Mechanical parameters | ||
| Overall dimension (L x W x H) (mm) | 400 x 240 x 260 | |
| Weight (kg) | ≤23 | |
| Environmental conditions | ||
| Relative humidity | 90RH% | |
| Operating temperature | -10°C to +40°C | |
| Altitude | ≤1000m | |
About the Supplier
Company Profile
Beijing GFUVE Electronics Co., Ltd. Was established in 2005. It combined science, industry and trade together as one high-tech enterprise. GFUVE mainly produces split core current transformer, high voltage ammeter recorder, IEC61850 test suite software, meter test equipment, current probe, reference standard meter, phantom load power source, electrical measurement instrument, relay test set, transformer test, CT analyzer, Test equipment, and power meter, power analyzer, intelligent digital meter, transducer, handheld terminal and split core current transformer, voltage transformer and current transformer models etc.
GFUVE is a leader manufacturer of energy meter test products and high voltage ammeter recorder in China. It is professional in energy meter test system, energy meter portable tester and related accessory of current probe. The product of high voltage ammeter recorder develops very quickly in the market. Our company has achieved certification to ISO9001. The products are sold to over 30 provinces in China and exported to overseas including South America, Middle East, South east and Africa.
We have been contributing ourselves to developing the durable and stable products for the usage of the power system. Contact us now for further business relationship. We are here to provide you the best service.
About Our Factory & Business Background
- Address
- Bldg. 2-1111, Joy Mansion, No. 99 Chaoyang North Road, Chaoyang District, Beijing, China
- Terms of Payment
- LC, T/T, PayPal, Western Union
- International Commercial Terms(Incoterms)
- FOB, CIF, FCA, EXW
- Average Lead Time
-
Peak Season Lead Time: one month
Off Season Lead Time: within 15 workdays - Nearest Port
- TIANJING
Our Production Capability & Technical Expertise
Our Industry Experience & Global Business Record
- Export Year
- 2010-08-01
- Main Markets
- North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe
FAQ
- What is the accuracy of this CT analyzer?
- The device offers high accuracy with options for 0.02% and 0.5%, ensuring precise measurements for both metering and protection classes.
- Can this device be used for field testing?
- Yes, it is designed as a portable analyzer with a built-in printer and USB data dumping capability, making it ideal for on-site testing.
- What types of transformers can be tested?
- It supports testing for Current Transformers (CT), Voltage Transformers (PT), and TYP class CTs, including ratio, polarity, and excitation tests.
- Does it comply with international standards?
- Yes, it meets IEC60044-1, IEC61869-2-2012, GB1207-2006, and GB1208-2006 standards for reference and safety.
- What is the maximum current output?
- The large current output can reach up to 1000A, suitable for comprehensive testing of various transformer types.
- How is data stored and printed?
- Data can be dumped using a USB flash disk, and the device is equipped with a mini type printer for immediate field printing.
Send your message to this supplier
People who viewed this also viewed
-
Negotiable
-
Negotiable
Find Similar Products By Category
- Supplier Homepage
- Products
- Transformer Test Equipment
- CT analyzer
- Current Transformer Tester Automatic Class 0.02 China High Quality Current Transformer CT Analyzer
Related Categories
Hot Searches
- High Current
- Current Voltage Factories
- Current Control Factories
- Current Protection Factories
- Type Current Transformer
- Low Current Transformer
- Standard Current Transformer
- Current Transformer Application
- Current Transformer Core
- Current Transformer Analyzer Bulkbuy