Test-901 1000a High Voltage Current Generator Current Injection Test Set
TEST-901 primary current injection test set adopts ARM Chip to control its output process and large capacity of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value, second current value, turn ratio and the action time. Packing is used as aluminum alloy body with PC panel. TEST-901 is mainly applied to CT turn ratio testing in the power system and contact resistance test which need large current.
Applications
1. Primary injection tests
2. Protective Relay Testing
3. Circuit Breaker Testing
4. Current Transformer Testing
5. Recloser and Sectionalizers
6. Switchgear Testing
7. Ground Grid Testing
Features
1. Permanent current up to 1000 A, 5KVA
2. Max current output up to 1100A
3. Built-in digital ammeter 0.5% accuracy
4. Built-in digital timer resolution 1ms
5. Small size, light weight, easy to test on-site
6. Thermal and short-circuit protection
Parameters
Electrical parameters |
|
Accuracy |
±0.5% |
Power Supply(AC) |
220V±10%·25A, 50Hz/60Hz or
110V±10%·50A, 50Hz/60Hz |
Current Output (AC) |
1000A·5V or 500A·10V |
Capacity |
5KVA |
The current output waveform distortion |
≤5% |
Dual protection |
overload electronic protection and software protection |
Primary current |
Range |
0-1100A |
Resolution |
0.1A |
Accuracy |
<0.5% |
Secondary measurement |
Range |
0-6A |
Resolution |
0.001A |
Accuracy |
<0.5% |
Current duration |
1000A range |
1000A 2-3minutes
500A 3-6minutes |
500A range |
500A 2-3minutes |
With timer |
Range |
0.0001~999.99S |
Resolution |
0.001S |
Accuracy |
<0.5%±5 words |
Mechanical parameters |
Dimensions (W×D×H) (mm) |
430×260×260 |
Weight(kg) |
25 |
Environmental conditions |
Temperature |
-10°C to 40°C |
Relative humidity |
≤80% |
Photo