DC Power Source Definition for Control Voltage Power Supply

Application: Thermal Power, Mechanical Instrument, Time Frequency Instrument, Electromagnetic Instrument
Power: Electricity
Certification: CE, CCC
Voltage Output: 1000V
Current Output: 36A
LCD Display: With LCD Display
Customization:
Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
GF6019
Customized
Customized
Accuracy Class
0.05%, 0.02%
Adjustment Range
(0-120)% Rg
Distortion Degree
Better Than 0.1% (Not Capacitive Load)
Load Capacity
Max 25va
Ripple Contents
≤1%
Full Load Regulation Rate
Less Than 0.01% Rg
Temperature Drift
8 Ppm/°c
Long-Term Stability
60 Ppm/Year
Transport Package
Standard Export Wooden Box
Specification
440x360x160
Trademark
GFUVE
Origin
Beijing
Production Capacity
200units/Day

Product Description

DC Power Source Definition  For Control Voltage Power Supply
It is suitable for electric power corporation measuring and testing center, power company and power plants
measuring department, national levels measuring and testing institutions, also suitable for railway, petroleum,
chemical industry and large industrial and mining enterprises, etc.
Features
1. Calibrating DC voltmeter, ammeter, power meter and DC transducer
2. Automatic range, used for testing the digital meter; Manual range, used for testing the DC indicator
3. As DC current source, voltage source, DC power source; it can output the standard DC voltage, DC current, DC power
4. 5.6 inch TFT color LCD screen, English display, easy to operate
5. It is built-in indicating meter and DC standard resource verification procedures
6. A wide range, covering for instrument often dosage limit
7. Use software calibration, stable and reliable
8. With RS232 interface, and computer software component semi-automatic verification system, data management, inquiry and print the inspection certificate and the inspection records
PARAMETERS
Electrical parameters  
Accuracy class  0.05%, 0.02%
Power supply Single phase AC 220V±10% or 110 V±10%, 50/60 Hz
DC Voltage output
Range 100mV, 300mV, 1V, 3V, 10V, 100V, 
300V, 600V, 1000V, (max 1000V)
Adjustment range (0-120)% RG
Adjustment resolution 0.01% RG, 0.1% RG, 1% RG, 10% RG
Accuracy 0.012% RD + 0.008% RG(≥1V); 0.03% RD + 0.02% RG(<1V)
Stability 0.005% RG / 1 min(≥1V); 0.01% RG / 1 min(<1V)
Distortion degree Better than 0.1% (not capacitive load)
Load Capacity Max 25VA
Ripple contents ≤1%
Full load regulation rate Less than 0.01% RG
Full load regulation time Less than 10mS
Temperature drift 8 PPM/°C
Long-term stability 60 PPM/year
DC Current output
Range 10uA, 30uA, 100uA, 300uA, 1mA, 3mA, 10 mA, 30mA, 
100mA, 300mA, 1A, 3A, 10A, 30A( max 36A)
Adjustment range (0-120)% RG
Adjustment resolution 0.01% RG, 0.1% RG, 1% RG, 10% RG
Accuracy 0.03% RD + 0.02% RG
Stability 0.01% RG/1 min
Distortion degree Better than 0.1% (not capacitive load)
Load Capacity 48VA
Ripple contents ≤1%
Full load regulation rate Less than 0.01% RG
Full load regulation time Less than 10mS
Temperature drift 8 PPM/°C
Long-term stability 60 PPM/year
DC Power output
Accuracy 0.05%
Stability 0.01% RG / 1 min
Mechanical parameters
Dimensions (W×D×H) (mm) 440x360x160 
Weight (kg) 12
Environmental conditions
Operating temperature 0°C to 40°C
Storage conditions -30°C to 60°C
Relative humidity ≤85%