Six Phase Universal Protection Device Relay Test Kit

Accuracy Grade: 0.1%
Display: Digital
Control: Computer Control
Weight: 19.8kg
Power Source: AC220V
Tpye: Protection Relay Test Kit
Customization:

Contact Supplier

Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
TEST-630
Accuracy
0.2%
Phase Current Output (Effective Value)
6X0~30A or 3X0~60A
Maximum Output Power
520va/Phase
Maximum Parallel Current Output
0~180A
Phase Current Output
6X0~25A or 3X0~50A
Voltage
460va/Phase
Max Parallel Current Output
0~150A
Phase Voltage Output
6X0~130V
Max Output Power
70va/Phase
Transport Package
Standard Export Carton
Specification
CE, ISO9001: 2008, IEC
Trademark
GFUVE
Origin
Beijing China
Production Capacity
100/Month

Product Description

TEST-630 Six Phase Universal Protection Device Relay Test Kit for Zero Sequence Protection


Six Phase Universal Protection Device Relay Test Kit
Six Phase Universal Protection Device Relay Test Kit
Six Phase Universal Protection Device Relay Test Kit

Overview

1. Six-channel current output
2. Six-channel voltage output
3. Six-channel share of DC current
4. Six-channel DC voltage output
5. Eight pairs of binary input
6. Four pairs of binary output.

Features

1. Integration in the host crystal 8.4 inches true color, light weight and easy to carry.
2. Built-in high-speed high-performance industrial computer, embedded operating system, running a stable and reliable; Also be connected PC testing.
3. Panel embedded user-friendly buttons can also be an external keyboard, mouse.
4. High-precision DAC to 12 Road, simultaneous output to ensure that waveform fitting of high precision, good linearity.
5. Matching electromagnetic compatibility components, can improve on-site anti-electromagnetic interference, protection devices can be connected electromagnetic compatibility tests.
6. Analog output of the front panel, switch the amount of terminal design in the upper cover, all the wiring does not affect the operation of the panels and test parameters of the surveillance.
7. Designed to the latest thermal structure, and to ensure the best ventilation. Automatically determine the over-current, over voltage, overload, short circuit, the temperature is too high, data anomalies and misuse warning prompt.
8. Using voltage, current amplifier AC / DC sharing, output stage uses a unique ultra-linear amplifier technology, high precision, good reliability; Six-phase AC output voltage and six-phase AC current.
9.12 analog ports and the other optional auxiliary DC source output (220V/110V).
10. Interface: RJ45 (Ethernet interface), USB interface (software upgrades, reporting transmission), industrial serial interface (GPS or other serial device use).
Functions
1. Host real-time operating system, fast response, when faced with an emergency situation, to better protection of instruments and equipment under test. Safe and reliable, not easy to be a computer virus violated.
2. Newly designed software interface style, Host machine operation is fully consistent with the background and easy.
3. Extensive testing capabilities: The state sequence determined in the trial, IT features analog oscillation, the entire group of tests, differential protection, harmonic superposition, low cycle load shedding, same equipment, measuring instruments, GPS synchronized debugging, fault playback, and custom test (special tests), etc., to satisfy various types of user testing microprocessor-based protection relay needs.
4. Easily complete the ABB, Siemens, AREVA and other foreign manufacturers of protective device test.
5. The test report can be easily derived from the USB port to print.
AC current output Phase current output (effective value) 6×0-30A or 3×0-60A
Maximum output power 520VA/phase
Maximum parallel current output (effective value) 0-180A
Long-term allowable working value of phase current (effective value) >10A
Allowable working time of maximum current >11s
Accuracy <±0.2%
AC voltage output Phase voltage output (effective value) 6×0-130V
Line voltage output (effective value) 0-260V
Maximum output power 70VA/phase
Accuracy <±0.2%
DC voltage output Output range 0-300V or 6×0-±130V
Maximum output power 130VA
Accuracy <±0.2%
DC current output Output range -10-10A or 6×0-±10A
Maximum output power 150VA
Accuracy <±0.2%
Binary input Idle contact 1-20mA, 24V (DC)
Electric potential contact 0-250V (DC)
Binary output Idle contact 250V/0.5A (DC)
Rated output Frequency error <±0.01Hz
Phase error <±0. 2°
Waveform distortion <±0.3% (fundamental wave)
Time error <40µs
Output frequency 0-1050Hz
Superposed harmonic wave 0-21times
Power voltage Allowable range AC220V±10%, 50Hz±10%
Ambient temperature Use range 0-45ºC
Storage range -25-70ºC
Time measurement Test range 0.1ms-999999.999s
Exterior appearance of cabinet Imported electromagnetic compatible cabinet, which is made of high-grade all aluminum alloy extruded section and has fine appearance, is selected.
Dimension of cabinet(L x W x H): 360mm ×195mm ×365mm
Weight of cabinet Weight of host machine 16.6kg
Load-bearing output Selectable between light load or heavy load output
(When any phase current output surpasses 15A, it is suggested to press key F3 before test of each functional module so as to switch to heavy load output mode)
 

Send your message to this supplier

*From:
*To:
avatar Mr. Andy Huang
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Product Groups

Contact Supplier

Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory
Registered Capital
5000000 RMB
Plant Area
>2000 square meters