TEST-630 3 phase relay test set supplier in malaysia
Product Description
Six Phase Universal protection device relay test kitt-Relay Tester-GFUVE Electronics
Test-630 automotive relay tester kit is a six phase current output and six phase voltage output protection relay tester with 5.Eight pairs of binary input and four pairs of binary output.
Features:
Integration in the host crystal 8.4 inches true color, light weight and easy to carry.
Built-in high-speed and high-performance industrial computer embedded operating system, running stable and reliable, also can test by connecting PC.
Panel embedded user-friendly buttons, and the panel can also be an external keyboard and mouse.
High-precision DAC to 12 Road, simultaneously output to ensure the high precision and good linearity of the waveform.
5Matching electromagnetic compatibility components, can improve on-site anti-electromagnetic interference, protection devices can connect the electromagnetic compatibility to test.
Analog output of the front panel, switch the amount of terminal design in the upper cover, all the wiring does not affect the operation of the panels and the test parameters of the surveillance.
The latest thermal structure design to ensure the best ventilation. Automatically determine over current, over voltage, overload and short circuit, if the temperature is too high, the anomalies and misuse warning of the data will show up promptly.
Using voltage, current amplifier AC / DC sharing, output stage uses a unique ultra-linear amplifier technology, high precision and reliability. six-phase AC output voltage and six-phase AC current.
12 analog ports and other optional auxiliary DC source output (220V/110V).
Interface: RJ45 (Ethernet interface), USB interface (software upgrades, reporting transmission), industrial serial interface (GPS or other serial device use).
Product Parameters
Electrical parameters |
Allowable range |
AC220V±10% or AC110V±10%, 50/60Hz±10% |
Time measurement |
0.1ms-999999.999s |
AC current output |
Phase current output (effective value) |
6×0-30A or 3 × 0-60A |
Maximum output power |
520VA/phase |
Maximum parallel current output (effective value) |
0-180A |
Long-term allowable working value of phase current (effective value) |
>10A |
Allowable working time of maximum current |
>11s |
Accuracy |
<±0.2% |
AC voltage output |
Phase voltage output (effective value) |
6×0-130V |
Line voltage output (effective value) |
0-260V |
Maximum output power |
70VA/phase |
Accuracy |
<±0.2% |
DC voltage output |
Output range |
0-300V or 6×0-±130V |
Maximum output power |
130VA |
Accuracy |
<±0.2% |
DC current output |
Output range |
-10-10A or 6×0-±10A |
Maximum output power |
150VA |
Accuracy |
<±0.2% |
Binary input |
Idle contact |
1-20mA, 24V (DC) |
Electric potential contact |
0-250V (DC) |
Binary output |
Idle contact |
250V/0.5A (DC) |
Rated output |
Frequency error |
<±0.01HzHz |
Phase error |
<±0. 2° |
Waveform distortion |
<±0.3% (fundamental wave) |
Time error |
<40µs |
Output frequency |
0-1050Hz |
Superposed harmonic wave |
0-21times |
Time measurement |
Test range |
0.1ms-999999.999s |
Mechanical parameters |
Dimensions (L×W×H) (mm) |
360×195×365 |
Weight (kg) |
16.6 |
Environmental conditions |
Use range |
0°C to 45°C |
Storage range |
-25°C to 70°C |