T-209 Circuit Breaker Tester can test the vacuum circuit breaker, SF6, oil circuit breaker, GIS and etc. the test parameters include, close or open time, delta time, bounce time, bounce cycles, multi-operation, stroke, gap, over-travel, overshoot, rebound and the speed, with the ability of test results and graph display.
The CB Analyzer system, is a new circuit breaker testing method that utilizes a Windows software program on a laptop or tablet pc to determine the condition of all types of circuit breakers.
circuit breaker analyzers are advanced standalone or a PC controlled instruments for circuit breaker maintenance. Typical application areas of CAT instruments are medium and high voltage substations at electric power generation, transmission, and factories of switchgear.
The T-209 is a multifunctional circuit breaker analyzer performing Motion, Timing and Dynamic Resistance Measurements, all in a single test. It has been the pioneer of fully computerized circuit breaker diagnosis, conceived for all kind of electrical facilities up to 800kV and more.
Circuit Breaker Analyzer - The GFUVE is an automatic timer and motion analyzer for medium- and high-voltage substation circuit breakers. It is intended for use on circuit breakers with one contact per phase.
Electrical parameters | ||
---|---|---|
Power supply | Single phase AC 220V±10% or 110V±10%, 50/60HzAC | |
Immunity | withstand the 550KV electrostatic environment | |
Test channels | 12 channels with 25V,the current is 50mA | |
Transducer | one analog transducer | |
TIME | Recording time length | 0~9.9s |
Recording time length | ±0.l%reading ± 2 LSB | |
Resolution | 0.1ms | |
Motion | Ranges | 0~1000mm |
Accuracy | ±1% reading ±1LSB | |
Resolution | 0.1mm | |
Velocity | Ranges | 0~20.00m/s |
Accuracy | ±1%reading ±1LSB | |
Resolution | 0.01m/s | |
DC POWER | Ranges | 15~260V |
Max current | 20A | |
Accuracy | ±1%reading ±1LSB | |
Load change | ≤1% | |
TRIGGER | Voltage | 15~260V |
Current | 0.1-20A | |
Transducer | the transducer states changes | |
Channels | channels states changed | |
Memory | SD card of 2GB,the maximum storage ability is 100 test results | |
Memory | ±1% reading ±1LSB | |
LCD | 5.7″black and white LCD display (320 x 240 pixels) | |
Communication | RS232 and USB communication interface | |
Printer | internal installed 58mm wide thermal printe | |
Standard | DL/T846.3-2004, IEC61010-1, IEC61326-1 | |
Mechanical parameters | ||
Dimension (L×W×H) (mm) | 380x262x120 | |
Weight (kg) | 6 | |
Environmental conditions | ||
Operating temperature | -10°C to 50°C | |
Storage temperrature | -20°C to 70°C | |
Relative humidity | ≤95%RH |