Customization: | Available |
---|---|
Accuracy: | 0.5% |
Insulation Voltage: | AC 2kv/Min.1mA (Between Input ~ Output / Power) |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
FUD-Type-Input-Power Supply-Range-Output | |
Type | Cosφ: Single phase power factor transducer 3Cosφ: 3P3W power factor transducer 4Cosφ: 3P4W power factor transducer |
AC Input | V0: 57V, V1: 100V, V2: 220V, V3: 270V, V4: 400V, V5: User defined; A1: 1A, A2: 5A |
Power Supply | P1: AC110V±10%, P2: AC220V±15%, |
PF Range | C1: 0(C)~1~0(L), C2: 0.5(C)~1~0.5(L), C3: 0~1 |
DC Output | O1: 0~5V, O2: 1~5V, O3: 0~20mA, O4: 4~20mA, O5: 0~5V, O6: 4~12~20mA, O9: RS485 |
Example 1: FUD-Cosφ-V2-A2-P2-C2-O6 | |
FUD Single phase power factor transducer | Input: AC220,5A |
Power: AC220V±15% | |
Range: 0.5(C) ~ 1 ~ 0.5(L) | |
Output: DC4~12~20mA | |
Example 2: FUD-3Cosφ-V2-A2-P2-C2-O6 | |
FUD 3P3W power factor transducer | Input: AC220,5A |
Power: AC220V±15% | |
Range: 0.5(C) ~ 1 ~ 0.5(L) | |
Output: DC4~12~20mA | |
Please check the Type, Input range, Output range and Power supply at your order. |
Standard | GB/T 13850-1998, IEC688:1992 |
Accuracy | 0.5% |
Consumption | ≤5VA |
Insulation Voltage | AC 2kV/min.1mA (Between Input ~ Output / Power) |
Insulation Resistance | ≥20MΩ (DC500V) |
Response Time | ≤300ms |
Input Range | AC 0~6A\0~380V(Optional), 50/60Hz |
Absorbed Power | Per phase Voltage:≤0.5VA/220V Per phase Current:<0.1VA/5A |
Overload | Current: 2 times continuous,30 times /1s .Voltage: 2 times continuous |
Load Resistance | Current output: RL≤650Ω Voltage output: RL≥2kΩ |
Working environment | Temperature: -10~50 RH: 20~90%, Without condensation |
Storage conditions | Temperature: -40~70 RH: 20~95%, Without condensation |
Installation | 35mm DIN Sliding-way or M4 screws |
Dimension | 110mm×75mm×120mm |