Warranty: | Three Years |
Maximum Output Power: | 520va/Phase |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Electrical parameters | |
---|---|
Allowable range | AC220V±10% or AC110V±10%, 50/60Hz±10% |
Time measurement | 0.1ms-999999.999s |
AC current output | |
Phase current output (effective value) | 6×0-30A or 3 × 0-60A |
Maximum output power | 520VA/phase |
Maximum parallel current output (effective value) | 0-180A |
Long-term allowable working value of phase current (effective value) | >10A |
Allowable working time of maximum current | >11s |
Accuracy | <±0.2% |
AC voltage output | |
Phase voltage output (effective value) | 6×0-130V |
Line voltage output (effective value) | 0-260V |
Maximum output power | 70VA/phase |
Accuracy | <±0.2% |
DC voltage output | |
Output range | 0-300V or 6×0-±130V |
Maximum output power | 130VA |
Accuracy | <±0.2% |
DC current output | |
Output range | -10-10A or 6×0-±10A |
Maximum output power | 150VA |
Accuracy | <±0.2% |
Binary input | |
Idle contact | 1-20mA, 24V (DC) |
Electric potential contact | 0-250V (DC) |
Binary output | |
Idle contact | 250V/0.5A (DC) |
Rated output | |
Frequency error | <±0.01HzHz |
Phase error | <±0. 2° |
Waveform distortion | <±0.3% (fundamental wave) |
Time error | <40µs |
Output frequency | 0-1050Hz |
Superposed harmonic wave | 0-21times |
Time measurement | |
Test range | 0.1ms-999999.999s |
Mechanical parameters | |
Dimensions (L×W×H) (mm) | 360×195×365 |
Weight (kg) | 16.6 |
Environmental conditions | |
Use range | 0°C to 45°C |
Storage range | -25°C to 70°C |