Customization: | Available |
---|---|
Power Supply: | AC 220V or 110V, 50/60Hz |
Test Current Range: | 5A to 10A |
Still deciding? Get samples of US$ 10000/Set
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Model | T-206 |
Rated working condition | environmental temperature: -10 ~ 50ºC Relative humidity: <85% |
Input power | 180V to 270VAC, 50Hz/60Hz + 1% |
Accuracy | Cx: + (reading * 1%+1pF)TG Delta: + (reading * 1%+0.00040) |
Anti-interference index | frequency conversion anti-interference, can achieve the accuracy under 200% interference |
Capacitance range | Internal applied high voltage: 3pF ~ 60000pF/10kV 60pF to 1 mu F/0.5kV External applied high voltage: 3pF to 1.5 F/10kV 60pF to 30 mu F/0.5kV |
Resolution | maximum 0.001pF, 4 bit significant digits |
TG delta range | no limit, resolution 0.001%, capacitance, inductance, resistance, three kinds of test products, automatic identification. |
Test current range | 10 A to 5A |
Internal Applied high voltage | set voltage range: 0.5 ~ 10kV |
Maximum output current | 200mA |
Lifting mode | continuous smooth adjustment |
Voltage accuracy | + (1%× readings +10V) |
Voltage resolution | 0.1V |
Test frequency | 45, 50, 55, 60, 65Hz single frequency 45/55Hz, 55/65Hz, 47.5/52.5Hz automatic dual frequency conversion |
Frequency accuracy | + 0.01Hz |
External applied high voltage | positive and reverse wiring, the maximum test current 5A |
CVT self excitation measurement | output voltage 3 ~ 50V, output current 3 ~ 30A C1/C2 simultaneous measurements, high-voltage wiring can be mopping |
CVT ratio measurement | change ratio measurement accuracy: + reading×1% ratio, measuring range: 10~99999 Phase measurement accuracy: + 0.02° phase measurement range: 0~ 359.99 ° |
High voltage dielectric loss | support frequency conversion and vibration supply, high voltage dielectric loss |
Real time clock | time and date display in real time |
Internal storage | 100 sets of measurement data can be stored inside the instrument |
U disk | supports U disk storage |
Printer | micro thermal printer |
Computer interface | Standard RS232 interface (optional) |
Size & weight | 368mm * 288mm * 280mm; main weight 22kg. |