• Gfuve Clamp on Current Probe P50 1000A Selected AC Measurement
  • Gfuve Clamp on Current Probe P50 1000A Selected AC Measurement
  • Gfuve Clamp on Current Probe P50 1000A Selected AC Measurement
  • Gfuve Clamp on Current Probe P50 1000A Selected AC Measurement
  • Gfuve Clamp on Current Probe P50 1000A Selected AC Measurement
  • Gfuve Clamp on Current Probe P50 1000A Selected AC Measurement

Gfuve Clamp on Current Probe P50 1000A Selected AC Measurement

Warranty: Three Years
Accuracy Class: 0.1%, 0.2%, 0.5%
Primary Current: 0 - 1000A AC
Weight (G): 550
Max. Jaw Opening (mm): 50
Transport Package: Standard Export Wooden Box
Samples:
US$ 150/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory
  • Overview
  • Product Description
  • Product Parameters
Overview

Basic Info.

Model NO.
P50
Specification
102.9 x 219.6 x 28
Trademark
GFUVE
Origin
Beijing, China
HS Code
90308490
Production Capacity
1000pieces/Month

Product Description

P50 1000A SELECTED AC MEASUREMENT CLAMP ON CURRENT PROBE

Gfuve Clamp on Current Probe P50 1000A Selected AC Measurement
 
Product Description

 



The round jaw design on the P50 Series AC current probes along with the high content nickel metal core makes them well suited for power quality applications where high accuracy and low phase shift along with wide frequency are important. Measurement range is 1mA to 1200A.
The P50 is a general purpose 1000A AC current probe designed for use with DMMs, loggers and other instruments that have a current input. It has a 1000:1 ratio and output of 1mA per amp or 1mV per amp measured in the jaw. The P50 has an integral 2.5m lead terminated. The rounded jaw design on this probe makes it well-suited for power applications where high accuracy 0.1% and low phase shift and wide frequency response are important.
 

FEATURES

  • Measurement range of 1mA to 1200A AC
  • Large jaw opening accommodates conductors up to two 500kcmil
  • Improved ergonomic design and easy operation
  • High content nickel metal core
  • Conforms to EN 61010, 600V CAT III
  • Low phase shift for power measurement
  • Designed for DMMs, recorders, loggers, oscilloscopes, power and harmonic meters
  • UL, CE mark
Product Parameters

 

Electrical parameters
Ratio 1000: 1 or 2000:1 (customized)
Accuracy class 0.1%, 0.2%, 0.5%
Primary current 0 - 1000A AC
Secondary current 1mV/A AC, 5mV/A or (customized)
Max. Cont. Input current 1200A
Over voltage category CAT III 600V
Output signal (AC current) 333mV, 500mV,1V,2V,5V AC at nominal input current
AC Accuracy(1000A Range)
0-10A ≤0.5%
10-100 ≤0.2%
10-1200A ≤0.1%
AC Phase Shift(1000A Range)
0-10A ≤0.5°
10-100 ≤0.2°
10-1200A ≤0.1°
Frequency range 40Hz-2000Hz
Dielectric strength 3KV 50Hz/60Hz at 1 minute
Temperature range -20°C to +55°C
Output 2.5 meter cable with D01 connector
Max. voltage not insulated conductors 600 V
Standard EN 61010-1, EN 61010-2-032, IEC60044-1
Installation Clamp type
Output mode Lead output (2.5m)
Mechanical parameters
Dimensions (L x W x H)(mm) 102.9 x 219.6 x 28
Weight (g) 550
Holding wire diameter (mm) φ50
Max. jaw opening (mm) 50
Color Gray or blue
Material PC+ABS+Polycarbonate, UL94 V0