Customization: | Available |
---|---|
Type: | Electric Instruments |
Output Signal Type: | Analog Output |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
FUD-Type-Input-Power Supply-Output |
|
Type |
P3: 3P3W Active Power Transducer Q3: 3P3W Reactive Power Transducer PQ3: 3P3W Active & Reactive Power Transducer |
AC Input |
V1: 100V, V2: 0~220V, V3: 270V, V4: 400V A1: 0~1A, A2: 0~5A. |
Power Supply |
P1: AC110V±10%, P2: AC220V±15%, P3: AC110V~330V. |
DC Output |
O1: 0~20mA, O2: 0~±20mA, O3: 4~20mA, O4: 4~12~20mA, O5: 0~1V, O6: 0~±1V, O7: 0~5V, O8: 0~±5V, O9: RS485. |
Example 1: FUD-P3-V1-A2-P2-O8 |
|
FUD Series 3P3W Active Power Transducer |
Input: AC100, ±5A , ±866W |
Power Supply: AC220V±15% |
|
Output: DC0~±5V |
|
Example 2: FUD-PQ3-V1-A2-P2-O8 |
|
Details: FUD Series 3P3W Active and Reactive Power Transducer |
Input: AC100V, ±5A , ±866W(var) |
Power Supply: AC220V±15% |
|
Output: DC0~±5V |
|
Please check the Type, Input range, Output range and Power supply at your order. |
Standard |
GB/T 13850-1998, IEC688:1992 |
Accuracy |
0.2%, 0.5% |
Consumption |
≤5VA |
Accutacy drift |
Annual Variation < 0.2% |
Insulation Voltage |
AC 2kV/min.1mA (Between Input ~ Output / Power) |
Insulation Resistance |
≥20MΩ (DC500V) |
Surge voltage |
5KV (Peak Value), 1.2/50μs |
Response Time |
≤350ms |
Input Range |
AC 0~5A ,AC 0~500V(Optional), 50/60Hz |
Absorbed Power |
Per phase Voltage:≤0.5VA/100V Per phase Current:<0.1VA/5A |
Overload |
Current: 2 times continuous,30 times /1s .Voltage: 2 times continuous |
Load Resistance |
Current output: RL≤650Ω Voltage output: RL≥2kΩ |
Working environment |
Temperature: -10~50°C RH: 20~90%, Without condensation |
Storage conditions |
Temperature: -40~70°C RH: 20~95%, Without condensation |
Installation |
35mm DIN Sliding-way or M4 screws |
Dimension |
110mm×75mm×120mm |